Plan Review Notes
Plan Review Notes For Permit 04040818
Permit Number 04040818
Review Stop M
Sequence Number 1
Notes
Date Text
2004-04-27 00:00:00NO MECHANICAL PLANS OR CONTRACTOR
 INDICATED WITH PERMIT APPLICATION.
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 WITH MECHANICAL PERMIT APPLICATION.
 1.PLANS - DUCT/GRILLE SIZE MATERIAL &
 LAYOUT.
  
 2.OUTSIDE AIR CALCULATIONS PER 2001
 FBC(M) TABLE 403.3.
  
 3.PROVIDE EQUIPMENT SCHEDULE.
  
 4.INDICATE CONDENSATE LINE SIZE,
 MATERIAL AND TERMINATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.