Plan Review Notes
Plan Review Notes For Permit 04040818
Permit Number 04040818
Review Stop E
Sequence Number 1
Notes
Date Text
2004-04-19 00:00:00********* UNSAT ***********
  
 1)NOTE: PLEASE SEE 2002 NEC 700.12E FOR
 CIRCUITING OF EM LTS.
 PLEASE SEE NOTE #6 MENTIONS TO WIRE
 AHEAD OF DISC. LOCAL BRANCH CIRCUITING
 IS REQ'D AHEAD OF ANY LOCAL DEVICE
 SWITCHING.
  
 2)NOTE; PLEASE BE SURE RAISED SEALED
 CAN BE CLEARLY VISABLE ON ALL SHEETS.
 SOME ARE VERY FAINT.
 FS 481.221.
  
 3)NOTE: MIN CIRCUITING WILL BE REQ'D ON
 PLANS ALONG WITH A PANEL SCHEDULE BEFORE
 FINAL. THIS MAY BE DONE AT THIS TIME TO
 AVOID REVISION FEES AT A LATER DATE.
  
 PLEASE SEE FIRE REVIEW COMMENTS THAT
 WILL AFFECT ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]