Plan Review Notes For Permit 04040818 |
Permit Number |
04040818 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-04-19 00:00:00 | ********* UNSAT *********** | | | | 1)NOTE: PLEASE SEE 2002 NEC 700.12E FOR | | CIRCUITING OF EM LTS. | | PLEASE SEE NOTE #6 MENTIONS TO WIRE | | AHEAD OF DISC. LOCAL BRANCH CIRCUITING | | IS REQ'D AHEAD OF ANY LOCAL DEVICE | | SWITCHING. | | | | 2)NOTE; PLEASE BE SURE RAISED SEALED | | CAN BE CLEARLY VISABLE ON ALL SHEETS. | | SOME ARE VERY FAINT. | | FS 481.221. | | | | 3)NOTE: MIN CIRCUITING WILL BE REQ'D ON | | PLANS ALONG WITH A PANEL SCHEDULE BEFORE | | FINAL. THIS MAY BE DONE AT THIS TIME TO | | AVOID REVISION FEES AT A LATER DATE. | | | | PLEASE SEE FIRE REVIEW COMMENTS THAT | | WILL AFFECT ELECTRICAL PLANS. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] |
|