Plan Review Notes For Permit 04040815 |
Permit Number |
04040815 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-04-19 00:00:00 | PROVISO: | | PLEASE NOTE RETURN AIR JUMPERS SHALL BE | | SIZED AS FOLLOWS: | | 1.MASTER BEDROOM RETURN SHALL BE 12". | | ALL AIR INTO THE MASTER SUITE IS TO BE | | INCLUDED FOR THE TOTAL OF SUPPLY AIR | | INTO THAT SPACE.REVISED 2001 FBC(M) | | 601.4 #1 & 3. | | | | 2.BEDROOM 1, RETURN AIR JUMPER SHALL | | BE A MINIMUM OF 8" PER REVISED 2001 | | FBC(M) 601.4 #1. | | | | 3.BEDROOM 2, RETURN AIR SHALL BE A | | MINIMUM OF 12". | | | | SEE THE ATTACHED SCHEDULE FOR PROPER | | SIZING FOR RETURN AIR. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|