Plan Review Notes For Permit 04040679 |
Permit Number |
04040679 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2004-06-01 00:00:00 | DENIED: | | RESPONSE LETTER FROM KAMM CONSULTING: | | DESIGN CAPACITY IS LESS THAN 2,000 CFM, | | THEREFORE DUCT SMOKE DETECTORS & ALARM/ | | STROBE IS NOT REQUIRED. | | | | PLEASE PROVIDE MANUFACTURER SUBMITTAL | | DATA FOR THE CARRIER AHU & CU #4. | | PROVIDE A LETTER FROM THE MANUFACTURER'S | | ENGINEER SPECIFYING UNDER NO CONDITIONS | | WILL THE EQUIPMENT EXCEED 2,000 CFM. | | THE LETTER SHALL BE SIGNED, SEALED & | | DATED BY THE ENGINEER. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|