2004-06-10 00:00:00 | BUILDING PLAN REVIEW | | PERMIT: 04020679 | | ADD: 2301 CENTREPARK DR# 175 | | CONT: LEIGHTON MC GINN | | TEL: (561)863-4455 | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | 2ND: REVIEW | | ACTION: DENIED | | | | 1) PROVIDE NOC RECORDED WITH THE CLERK | | OF COURT BEFORE A PERMIT CAN BE ISSUED. | | | | 2) NOTE 4 FROM PREVIOUS REVIEW, | | DOOR 119. 1012.4 DURING ITS SWING, ANY | | DOOR IN A MEANS OF EGRESS SHALL LEAVE | | UNOBSTRUCTED AT LEAST ONE HALF OF THE | | REQUIRED WIDTH OF A CORRIDOR, PASSAGEWAY | | OR LANDING. PLANS INDICATE THE PASSAGE- | | WAY TO BE 4'-0"WIDE. THE DOOR SCHEDULE | | INDICATES THE DOOR IS 3'-0" WIDE. THE | | CLEAR FLOOR SPACE LEFT IS 12". THE MINI- | | MUM CORRIDOR WIDTH IS 36" FOR LESS THAN | | 50 OCCUPANTS TABLE 1004, FOOTNOTE # 10. | | THE MINIMUM CLEAR WIDTH WHEN THE DOOR IS | | OPEN IS 18". THE MINIMUM CORRIDOR WIDTH | | WOULD BE 4'-6" FOR A OCCUPANT LOAD LESS | | THAN 50. | | BUILDING PLAN REVIEW | | JIM WITMER | | TEL: (561)805-6715 | | FAX: (561)659-8026 |
|