2004-06-10 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04020679
 ADD: 2301 CENTREPARK DR# 175
 CONT: LEIGHTON MC GINN
 TEL: (561)863-4455
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 2ND: REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) NOTE 4 FROM PREVIOUS REVIEW,
 DOOR 119. 1012.4 DURING ITS SWING, ANY
 DOOR IN A MEANS OF EGRESS SHALL LEAVE
 UNOBSTRUCTED AT LEAST ONE HALF OF THE
 REQUIRED WIDTH OF A CORRIDOR, PASSAGEWAY
 OR LANDING. PLANS INDICATE THE PASSAGE-
 WAY TO BE 4'-0"WIDE. THE DOOR SCHEDULE
 INDICATES THE DOOR IS 3'-0" WIDE. THE
 CLEAR FLOOR SPACE LEFT IS 12". THE MINI-
 MUM CORRIDOR WIDTH IS 36" FOR LESS THAN
 50 OCCUPANTS TABLE 1004, FOOTNOTE # 10.
 THE MINIMUM CLEAR WIDTH WHEN THE DOOR IS
 OPEN IS 18". THE MINIMUM CORRIDOR WIDTH
 WOULD BE 4'-6" FOR A OCCUPANT LOAD LESS
 THAN 50.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026