Plan Review Notes
Plan Review Notes For Permit 04040679
Permit Number 04040679
Review Stop M
Sequence Number 1
Notes
Date Text
2004-04-22 00:00:00DENIED:
 PER 2001 FBC(M) 606.2.1, DUCT SMOKE
 DETECTORS ARE REQUIRED IN SYSTEMS THAT
 HAVE THE DESIGN CAPACITY GREATER THAN
 2,000 CFM.PROVIDE LETTER FROM
 MANUFACTURERS ENGINEER INDICATING THAT
 UNDER NO CIRCUMSTANCE, WILL AHU-4 BE
 ABLE TO PROVIDE GREATER THAN 2,000 CFM.
  
 FAN SHUTDOWN SHALL HAVE NOTIFICATION TO
 ALARM/STROBE IN NORMALLY OCCUPIED AREAS.
 2001 NFPA 90A 6.4.4.3 (1).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.