Plan Review Notes For Permit 04040679 |
Permit Number |
04040679 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-04-22 00:00:00 | DENIED: | | PER 2001 FBC(M) 606.2.1, DUCT SMOKE | | DETECTORS ARE REQUIRED IN SYSTEMS THAT | | HAVE THE DESIGN CAPACITY GREATER THAN | | 2,000 CFM.PROVIDE LETTER FROM | | MANUFACTURERS ENGINEER INDICATING THAT | | UNDER NO CIRCUMSTANCE, WILL AHU-4 BE | | ABLE TO PROVIDE GREATER THAN 2,000 CFM. | | | | FAN SHUTDOWN SHALL HAVE NOTIFICATION TO | | ALARM/STROBE IN NORMALLY OCCUPIED AREAS. | | 2001 NFPA 90A 6.4.4.3 (1). | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|