2004-04-17 00:00:00************* UNSAT ***************
  
 1)NOTE: PLEASE SEE FIRE REVIEW COMMENTS
 FOR DOORS OPENING INTO EGRESS.
 PLEASE SEE THAT THIS COMMENT MAY HAVE
 AN AFFECT ON LAY OUT AND/OR ELECTRICAL.
  
 2)NOTE: PLEASE INDICATE AIC RATING FOR
 NEW 200A MAIN AT METER. 110.9
 SHOWN FOR NEW PANELS.
  
 3) NOTE: PLEASE SHOW ALL CONTINUOUS LOAD
 -S AT 125%(LIGHTING ETC)(LARGEST MOTORS)
 215.2,215.3,230.42 ETC
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  