Plan Review Notes For Permit 04040670 |
Permit Number |
04040670 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2004-06-03 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 CHAPTER 1 | | FBC-2001 CHAPTER 11 | | FLORIDA ADMINISTRATIVE CODE | | FLORIDA STATUTES | | | | 1) FROM PREVIOUS REVIEW: SHOW LOCATION | | OF WATER COOLER. WATER COOLER SHALL CON- | | FORM TO ARI-1010. SUBMIT MANUF. SPECIFI- | | CATION SHEETS INDICATING ARI-1010 COM- | | PLIANCE. SECTION 410.1. | | 2) FROM PREVIOUS REVIEW: KITCHENETTE | | SINK. SHOW COMPLIANCE WITH SECTION | | 11-4.24.3 KNEE CLEARANCE. AT LEAST 27" | | AND 19" DEEP REQUIRED. - 11-4.24 DEPTH | | OF SINK SHALL BE 6-1/2" DEEP MAX. - AND | | 11-4.24.6 EXPOSED PIPES AND SURFACES NOT | | SHOWN. | | 3) A TURNING AREA COMPLYING WITH 11-4.2. | | 3 IS REQUIRED FOR KITCHENETTE SINK. SEE | | FIGURES 3A OR 3B. | | 4) SEE COMMENTS FROM ELECTRICAL PLAN | | REVIEW CONCERNING SIGNATURE REQUIREMENTS | | FOR ENGINEER. FAC 61G15-23.002(1)(2) & | | FS 471.025. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|