Plan Review Notes
Plan Review Notes For Permit 04040670
Permit Number 04040670
Review Stop E
Sequence Number 1
Notes
Date Text
2004-04-17 00:00:00*********** UNSAT *****************
  
 1)NOTE: PLEASE HAVE ENGINEER SIGN PLANS.
 SIGNATURE DOES NOT SEEM TO BE THE SAME
 AS PREVIOUS PLANS WE HAVE REVIEWED AND
 PLUMB PLANS ALSO. FS 471.025
 PLEASE PROVIDE A COPY OF LEGAL LICENSE/
 AND/OR DRIVERS LICENSE TO VERIFY SIGNAT-
 -URE. ANY PERSONNEL INFORMATION ON DL
 MAY BE CROSSED OUT.
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
 SHOWN FOR NEW PANEL(S), BUT NOT FOR
 MAINS.
  
 3)NOTE: PLEASE SEE 250.66 FOR SIZING
 OF GROUNDING ELECTRODE.
  
 4)NOTE: PLEASE CORRELATE PLANS WITH
 RISER DIAGRAM. PLANS ONLY SHOW A METER
 ON BLDG. IS THE SERVICE IN ANOTHER
 LOCATION?
  
 5)NOTE: PLEASE LABEL CLEAR FLOOR SPACE
 FOR PANELS IN STORAGE AREA.110.26
  
 6) NOTE: PLEASE SHOW ALL CONTINUOUS LOAD
 -S AT 125%(LIGHTING ETC)(LARGEST MOTORS)
 215.2,215.3,230.42 ETC
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]