Plan Review Notes
Plan Review Notes For Permit 04040670
Permit Number 04040670
Review Stop B
Sequence Number 1
Notes
Date Text
2004-04-27 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04040670
 ADD: 515 PALM ST
 CONT: BURKHARDT CONSTRUCTION
 TEL: (561)659-1400
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) FRONT DOOR & SIDELIGHT
 B) STORM SHUTTERS
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 3)TABLE 704.1 OCCUPANCY SEPERATION
 REQUIREMENTS; GULF STREAM MARINE, THE
 WALL SEPERATING THE WAREHOUSE FROM THE
 OFFICE ALSO NEEDS TO HAVE A 2HR RATING.
 SEE 704.2.2(4) IF THE OFFICE SPACE COMPL
 IES WITH SECTION ABOVE (< 1/3RD OF THE
 MAJOROCCUPANCY FLOOR AREA IN WHICH IT IS
 LOCATED, THEN NO RATING WOULD BE NECESS-
 ARY. AS DESIGNED THE DOOR SEPERATING THE
 OFFICE FROM THE WAREHOUSE NEEDS TO BE
 A 1 1/2 HR RATING.
  
 4)NEW KITCHENETTE SINK HEIGHT MAX. 34"
 11-4.24.2
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026