Plan Review Notes
Plan Review Notes For Permit 04040629
Permit Number 04040629
Review Stop E
Sequence Number 1
Notes
Date Text
2004-04-17 00:00:00*********** UNSAT ***************
  
 1)NOTE: PLANS REQ'D TO BE ORIG SIGNED,
 DATED AND SEALED PER FS 471.025, FAC 61G
 15-23.002
  
 2)NOTE: PLEASE CORRELATE PLANS/WIRING
 DIAGRAM WITH ALL EQUIPMENT BEING INSTALL
 -ED. HEAT PUMP ETC.
  
 3)NOTE: PLEASE SUBMIT SPECS FOR HEAT
 PUMP. PLEASE BE SURE LISTING IS INDICAT-
 -ED.
  
 4)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 FOR EXSITING SERVICE AND INCLUDE ALL
 NEW LOADS BEING ADDED. SIZE OF EXIST
 SERVICE.
  
 5)NOTE: PLEASE INCLUDE ALL LICENSE #'S
 ON TITLE BLOCK AS REQ'D UNDER FAC 61G15-
 -23.002
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]