Plan Review Notes
Plan Review Notes For Permit 04040562
Permit Number 04040562
Review Stop M
Sequence Number 7
Notes
Date Text
2006-05-15 00:00:00DENIED:
 1.PLAN SHEET M-2.1, EF-1 IS NOW
 TERMINATING AT THE FIRST FLOOR WALL.
 PLAN SHEET M-2.2 AND M-2.3 INDICATE EF-1
 STILL TERMIATING AT THE ROOF.PLEASE
 REVISE PLANS TO REFLECT THE PROPER
 TERMINATION.
  
 2.PLAN SHEET M-2.1, SUPPLY & RETURN
 DUCTS TO RTU-1 ARE REQUIRED TO HAVE FIRE
 DAMPERS AT THE FLOOR WHERE THEY LEAVE
 THE RATED SHAFT IN ACCORDANCE WITH 1999
 NFPA 90A 3-3.4.4 & 2001 FBC 705.6.4.
  
 3.COMMENT #2 ALSO APPLIES TO PLAN
 SHEET M-2.2 2ND FLOOR WHERE THE DUCT
 PASSES THROUGH THE RATED FLOOR FROM
 RTU-2.PLEASE REVISE PLANS TO INDICATE
 ALL FIRE DAMPER/ACCESS DOORS FOR ALL
 RTU'S.
  
 4.PLEASE NOTE, SHOULD THE EXHAUST
 SHAFTS FOR EF-3 & EF-2 BE A SUB-DUCT
 METHOD, FIRE DAMPERS WILL NOT BE
 REQUIRED.PLEASE CLARIFY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.