2004-08-06 00:00:00 | BUILDING PLAN REVIEW |
| *******DENIED******* |
| ROBERT BROWN(561) 805 6716 |
| E-MAIL: [email protected] |
| |
| FBC = FLORIDA BUILDING CODE 2001 |
| FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| |
| FOR CONSISTENCY, THE FOLLOWING COMMENTS |
| ARE NUMBERED AS PER THE BUILDING PLAN |
| REVIEW OF 7/20/04: |
| |
| 7) THIS COMMENT HAS NOT BEEN PROPERLY |
| ADDRESSED. |
| FBC 13-103.1.2BEFORE A BUILDING |
| PERMIT CAN BE ISSUED, SHEET 2 OF THE |
| SUBMITTED ENERGY CODE COMPLIANCE FORMS |
| SHALL BE SIGNED BY THE BUILDING OWNER, |
| OWNER'S ARCHITECT OR OTHER AUTHORIZED |
| AGENT LEGALLY DESIGNATED BY THE OWNER. |
| ALSO, SHEET 1 SHALL STATE THE OWNER'S |
| NAME. |
| |
| 29) PRODUCT APPROVAL: |
| (A) CASEMENT WINDOW PRODUCT APPROVAL |
| NOA# 03-1006.08 STATES "SMALL MISSILE |
| IMPACT" RATING.AS THEY ARE NOT RATED |
| FOR LARGE MISSILE IMPACT, ALL CASEMENT |
| WINDOWS LESS THAN 30 FEET ABOVE GRADE |
| WILL REQUIRE HURRICANE SHUTTERS. |
| ALTERNATIVELY SUBMIT A PRODUCT APPROVAL |
| FOR WINDOWS WITH LARGE MISSILE IMPACT |
| RATING. ALSO, THE SUBMITTED NOA IS NOT |
| APPROPRIATE FOR THE 2ND AND 3RD FLOOR |
| 45 MINUTE FIRE-RATED WINDOWS UNLESS A |
| FIRE RESISTANCE TEST REPORT IS SUBMITTED |
| FIRE-RATED WINDOWS SHALL NOT BE OPENABLE |
| EXCEPT FOR MAINTENANCE ONLY (SEE ALSO |
| COMMENT (B) BELOW). |
| (B) ROLL-UP SHUTTER PRODUCT APPROVAL |
| NOA# 03-0106.16 STATES THAT THE "ROLL-UP |
| MECHANISM IS NOT PART OF THIS APPROVAL". |
| HOW ARE THESE SHUTTERS TO BE DEPLOYED |
| OVER THE 2ND AND 3RD FLOOR WINDOWS?THE |
| PROPOSED CASEMENT WINDOWS OPEN OUTWARD |
| AND WOULD OBSTRUCT SHUTTER DEPLOYMENT |
| WITH THE WINDOW OPEN (SEE COMMENT (A) |
| ABOVE).ALSO, THERE IS ONLY 2 FEET |
| (APPROX.) FROM THEBUILDING TO THE |
| WEST PROPERTY LINE IF THE SHUTTERS ARE |
| TO BE DEPLOYED FROM OUTSIDE.IF THE |
| SHUTTERS ARE TO BE MOTOR DRIVEN, THE |
| PLANS SHALL STATE THIS. |
| |
| 34) FBC* 105.13.1SPECIAL INSPECTOR. |
| A SIGNED AND SEALED COPY OF THE SPECIAL |
| INSPECTOR AGREEMENT AND AFFADAVIT SHALL |
| BE SUBMITTED BEFORE A PERMIT CAN BE |
| ISSUED.A PRE-CONSTRUCTION MEETING WITH |
| THE OWNER, CONTRACTOR, INSPECTION |
| COMPANY AND ON-SITE INSPECTOR SHALL BE |
| ARRANGED BY CALLING HAROLD PISKURA ON |
| 561 805 6711. |
| |
| **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| |
| END OF REVIEW COMMENTS |
| THE CODE REFERENCES GIVE ADDITIONAL INFO |
| TELEPHONE: (561) 805 6716ROBERT BROWN |
| E-MAIL: [email protected] |