2006-06-25 00:00:00 | BUILDING PLAN REVIEW |
| *******DENIED******* |
| ROBERT BROWN(561) 805 6652 |
| E-MAIL: [email protected] |
| |
| REVISION SUBMITTED 4/18/06 FOR ROLL-UP |
| SHUTTERS AND FOR METAL TRUSS DETAILS. |
| |
| FBC = FLORIDA BUILDING CODE 2001 |
| FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| F.S.= FLORIDA (STATE) STATUTE |
| |
| REVISION DENIED |
| |
| 1) FBC 1606.1ROLL-UP SHUTTERS.THE |
| SUBMITTED TOWN AND COUNTRY INDUSTRIES |
| ROLL-UP SHUTTER PRODUCT APPROVAL |
| FL2251-R1 HAS MULTIPLE OPTIONS FOR SLAT |
| SPAN, ANCHOR TYPE, STORM BAR, MULLION |
| AND HEADER.THE PRODUCT APPROVAL CANNOT |
| BE REVIEWED UNTIL IT HAS BEEN MARKED TO |
| SHOW WHICH OPTIONS ARE BEING PROPOSED. |
| MARK THE PRODUCT APPROVAL WITH THE |
| PROPOSED OPTIONS PRIOR TO RESUBMITTAL. |
| |
| 2) FBC 1606.1METAL TRUSSES.ALL THREE |
| OF THE TRUSS DETAIL SHEETS SPECIFY THE |
| USE OF SIMPSON MTSM16 AND/OR MTSM20 |
| TWIST STRAPS TO ANCHOR THE METAL |
| TRUSSES.PER THE SIMPSON LITERATURE, |
| THESE ANCHORS ARE DESIGNED TO ANCHOR |
| WOOD TRUSSES TO CMU OR CONCRETE.THE |
| CAPACITIES GIVEN IN THE LITERATURE ARE |
| FOR WOOD TRUSSES.HOW WILL THESE STRAPS |
| BE FASTENED TO THE DOUBLE METAL STUDS |
| WHICH ARE BACK-TO-BACK?THE SIMPSON |
| CATALOG SPECIFIES 8-10D (FOR MTSM16) OR |
| 10-10D (FOR MTSM20) INTO WOOD TRUSSES. |
| WHAT IS THE PROPOSED MEANS OF FASTENING |
| THE TWIST STRAPS TO THE 18 GAUGE METAL |
| TRUSSES?RATIONAL ANALYSIS WILL BE |
| REQUIRED TO JUSTIFY THE UPLIFT |
| RESISTANCE OF THE TWIST STRAP-TO-TRUSS |
| CONNECTION. |
| |
| **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| |
| END OF REVIEW COMMENTS |
| THE CODE REFERENCES GIVE ADDITIONAL INFO |
| TELEPHONE: (561) 805 6652ROBERT BROWN |
| E-MAIL: [email protected] |