Plan Review Notes
Plan Review Notes For Permit 04040562
Permit Number 04040562
Review Stop M
Sequence Number 3
Notes
Date Text
2004-07-07 00:00:00PROVISO:
 RESPONSE TO PROVISO DATED JUNE 24,2004;
 SHAFT INDICATED ON THE ARCHITECTURAL
 DRAWINGS.PLAN DOES NOT INDICATE FIRE
 DAMPERS ON THE DUCT PENTRATING THE SHAFT
 WALLS ON FLOORS 1 THROUGH 3.
  
 FAN SHUT DOWN BY DUCT SMOKE DETECTORS
 REQUIRED PER 2001 FBC(M) 606.2.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.