Plan Review Notes
Plan Review Notes For Permit 04040562
Permit Number 04040562
Review Stop B
Sequence Number 26
Notes
Date Text
2006-06-01 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6652
 E-MAIL: [email protected]
  
 STRUCTURAL REVISION SUBMITTED 5/25/06
 FOR SKYLIGHT CURB DETAIL.
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 REVISION DENIED:
 1) THE PROPOSED CURB DETAIL BEARS NO
 RESEMBLANCE TO THE ATTACHMENT DETAIL
 SHOWN IN THE SKYLIGHT PRODUCT APPROVAL.
 THE SKYLIGHT SHALL BE INSTALLED IN
 ACCORDANCE WITH THE DETAIL SHOWN ON
 SHEET E4 OF THE SUBMITTED NATURALITE
 SKYLIGHTS PRODUCT APPROVAL NOA#
 01-0118.08 (FL# 1500)
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6652ROBERT BROWN
 E-MAIL: [email protected]