Plan Review Notes
Plan Review Notes For Permit 04040562
Permit Number 04040562
Review Stop B
Sequence Number 25
Notes
Date Text
2006-05-12 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6652
 E-MAIL: [email protected]
  
 REVISION SUBMITTED ON 4/14/06 FOR
 SKYLIGHT PRODUCT APPROVAL AND
 PLANS/PRODUCT APPROVAL FORAPPLICATION
 OFROOFING SYSTEM TO THE METAL DECK
 OMITTING THE CONCRETE SLAB.
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
  
 1) SHEETS A3.1 AND A3.2 WERE REVISED BUT
 SHEET A1.1.4.1, DETAILS 05 AND 08, AND
 SHEET A3.2.1, DETAILS 01, 02 1ND 06 ALSO
 MAKE SPECIFIC REFERENCE TO 'CONCRETE
 SLAB ON METAL DECK'.THESE SHEETS MUST
 ALSO BE AMENDED FOR CONSISTENCY.
  
 2) THE REVISED SHEETS REFER TO 'BUILT UP
 ROOF' WHILE THE SUBMITTED PRODUCT
 APPROVAL IS FOR 'MODIFIED BITUMEN ROOF
 SYSTEM'.AMEND THE PLANS TO CORRECTLY
 STATE THE TYPE OF ROOF SYSTEM TO BE USED
 (I.E. MODIFIED BITUMEN ROOF).
  
 3) RATIONAL ANALYSIS REQUIRED PER
 MODIFIED BITUMEN ROOF PRODUCT APPROVAL.
 THE SUBMITTED GAF MODIFIED BITUMEN
 ROOFING PRODUCT APPROVAL NOA# 03-0430.12
 WAS MISSING SHEETS 1 TO 3 AND THE STATE
 PRODUCT APPROVAL COVER SHEET FL# 617-R1.
 THESE HAVE BEEN PRINTED FOR YOU TO
 EXPEDITE THE PROCESS.ON SHEET 13 OF
 THE NOA, THE STATED MAXIMUM DESIGN
 PRESSURE IS -60 PSF, WHICH IS ADEQUATE
 TO RESIST THE -43 PSF CALCULATED
 PRESSURE, STATED ON STRUCTURAL PLAN
 SHEET S1.0, FOR ZONE 1 (FIELD) OF THE
 ROOF.AS STATED ON SHEET 13 OF THE NOA,
 THAT IS ACHIEVED USING A FASTENER
 DENSITY OF 1 FASTENER PER 1.5 SQUARE
 FEET FOR ATTACHMENT OF THE INSULATION TO
 THE METAL DECK.HOWEVER, FOR ZONES 2
 AND 3, STRUCTURAL PLAN SHEET S1.0 STATES
 THAT THE CALCULATED PRESSURES ON THE
 BUILDING ARE -73 PSF AND -107 PSF
 RESPECTIVELY.ALTHOUGH THESE PRESSURES
 EXCEED THE ALLOWABLE -60 PSF MAXIMUM
 DESIGN PRESSURE STATED ON SHEET 13 OF
 THE NOA, THAT SHEET REFERS TO GENERAL
 LIMITATION #7.ON SHEET 31 OF THE NOA,
 GENERAL LIMITATION #7 ALLOWS RATIONAL
 ANALYSIS TO DETERMINE THE INCREASED
 FASTENER DENSITY REQUIRED TO RESIST THE
 -73 PSF AND -107 PSF WIND PRESSURES IN
 ZONES 2 AND 3.NO RATIONAL ANALYSIS WAS
 SUBMITTED.SUBMIT CALCULATIONS STATING
 THE FASTENER INSULATION LAYER FASTENER
 DENSITY.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS