2004-06-18 00:00:00 | BUILDING PLAN REVIEW |
| *******DENIED******* |
| ROBERT BROWN(561) 805 6716 |
| E-MAIL: [email protected] |
| |
| FBC = FLORIDA BUILDING CODE 2001 |
| FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| |
| FOR CONSISTENCY, THE FOLLOWING COMMENTS |
| ARE NUMBERED AS PER THE BUILDING PLAN |
| REVIEW OF 5/13/04: |
| |
| 1) COMMENT RESPONSE ON 5/20/04 IS NOTED. |
| THE NOTICE OF COMMENCEMENT SHALL BE |
| RECORDED AT PALM BEACH COUNTY COURTHOUSE |
| AND A COPY SUBMITTED TO THIS OFFICE |
| BEFORE A PERMIT CAN BE ISSUED.BLANK |
| FORMS ARE AVAILABLE FROM THIS OFFICE. |
| |
| 2) COMMENT RESPONSE ON 5/20/04 IS NOTED. |
| IMPACT FEES. THE PLANS SHALL BE TAKEN |
| TO PALM BEACH COUNTY BUILDING DEPARTMENT |
| FOR IMPACT FEE ASSESSMENT. THEY SHALL BE |
| STAMPED AT THAT OFFICE AND A COPY OF THE |
| PAID RECEIPT SUBMITTED TO THE CITY OF |
| WEST PALM BEACH DEPT OF CONSTRUCTION |
| SERVICES BEFORE A PERMIT CAN BE ISSUED. |
| |
| 3) FBC* 104.6.5BUILDING PERMIT |
| VALUATION.AS 2ND, 3RD AND 4TH FLOORS |
| ARE TO BE LEFT AS 'SHELL ONLY', FOR |
| LATER BUILD-OUT, THE CALCULATED VALUE |
| FOR PERMIT FEE ASSESSMENT HAS BEEN |
| REDUCED TO $1,239,456.THE OUTSTANDING |
| FEES MUST BE PAID BEFORE A PERMIT CAN BE |
| ISSUED. |
| |
| 4) FBC* 104.1.5BUILDING ADDRESS.THE |
| COMMENT RESPONSE ON 5/20/04 IS NOTED. |
| THE SHEETS THAT WERE REVISED IN RESPONSE |
| TO COMMENTS NOW SHOW THE CORRECT ADDRESS |
| (307 EVERNIA ST).THOSE SHEETS THAT |
| WERE NOT REVISED STILL SHOW THE WRONG |
| ADDRESS.THE REQUIRED ADDRESS AMENDMENT |
| MAY BE MADE TO EACH TITLE BLOCK BY HAND. |
| |
| 5) FBC* 104.2.4SITE SURVEY.THE |
| COMMENT RESPONSE ON 5/20/04 IS NOTED. |
| THE SUBMITTED SURVEY DRAWINGS DO NOW |
| HAVE AN ORIGINAL SIGNATURE BUT THEY ARE |
| NOT PROPERLY SEALED.THE DRAWINGS SHALL |
| BE RE-SEALED(REF: 472.025(1) F.S.) |
| |
| 7) FBC 13-103.1.2 ENERGY CODE COMPLIANCE |
| FORM.THE COMMENT RESPONSE LETTER DATED |
| 5/20/04 IS NOTED: |
| (A) BEFORE A BUILDING PERMIT CAN BE |
| ISSUED, SHEET 2 OF SUBMITTED ENERGY CODE |
| COMPLIANCE FORMS SHALL BE SIGNED BY THE |
| BUILDING OWNER, THE OWNER'S ARCHITECT OR |
| OTHER AUTHORIZED AGENT LEGALLY |
| DESIGNATED BY THE OWNER. |
| (B) THE PROJECT INFORMATION ON EACH COPY |
| OF SHEET 1 SHALL INCLUDE THE CORRECT |
| PROJECT ADDRESS (307 EVERNIA ST) AND ZIP |
| CODE (33401), THE PERMIT NUMBER |
| (04040562) AND THE OWNER'S NAME. |
| (C) FBC 13-103.1.1.1THE ARCHITECT'S |
| LICENSE NUMBER AND THE LIGHTING SYSTEM |
| DESIGNER'S NAME AND LICENSE NUMBER SHALL |
| BE ADDED TO SHEET 2 OF EACH COPY OF THE |
| ENERGY CODE COMPLIANCE FORM. |
| |
| 11) FBC 1006.2.2EXTERIOR EXIT STAIR. |
| THE COMMENT RESPONSE ON 5/20/04 IS NOTED |
| REFERING TO THE ADDITION OF A NOTE. BUT, |
| SHEETS LS1.2 AND A1.2 SHALL BE AMENDED |
| TO SHOW THOSE OPENINGS IN THE EXISTING |
| BUILDING THAT ARE WITHIN 10 FEET OF THE |
| EXTERIOR EXIT STAIR AND ANNOTATED TO |
| STATE THE REQUIREMENT FOR 3/4 HOUR FIRE- |
| RESISTANT DOORS AND WINDOWS IN SUCH |
| OPENINGS.ALSO THE PLANS SHALL BE |
| AMENDED TO SHOW WHETHER EITHER OF THE |
| ADJACENT BUILDINGS HAVE EXITS LEADING TO |
| THIS EXTERIOR STAIR. |
| |
| 12) FBC 1007.5SHEET A4.1, STAIR #2 |
| SECOND FLOOR PLAN.THE COMMENT RESPONSE |
| ON 5/20/04 IS NOTED.THE AMENDED PLANS |
| STILL DO NOT GIVE ANY DETAILS FOR A |
| HANDRAIL ON EXISTING STAIR FLIGHT FROM |
| FIRST TO SECOND FLOOR.AMEND THE PLANS |
| TO DEMONSTRATE COMPLIANCE. |
| |
| 14) SHEET S2.4STAIR SUPPORT.THE |
| COMMENT RESPONSE ON 5/20/04 IS NOTED |
| EXPLAINING THE STRINGER AND LANDING |
| SUPPORT AGAINST THE WALL USING ANCHORS. |
| IT IS STILL NOT CLEAR WERE SHEET S2.4 |
| CONCRETE PADSTONE DETAIL APPLIES TO. |
| WHY DOES THE COMMENT RESPONSE LETTER |
| REFER TO "EXTERIOR MECHANICAL PAD"? |
| ADD A TITLE TO THE CONCRETE PADSTONE |
| DETAIL TO CLARIFY. |
| |
| 16) FBC 1608.2.2GUARDRAIL STRENGTH. |
| THE COMMENT RESPONSE, DATED 5/20/04, IS |
| NOTED BUT IS APPLICABLE TO HANDRAILS |
| ONLY.THE LOADING FOR GUARDRAIL DESIGN |
| IS DIFFERENT.THE GUARDRAILS SHALL BE |
| DESIGNED AND CONSTRUCTED FOR A |
| CONCENTRATED LOAD OF 200 LB APPLIED IN |
| ANY DIRECTION AT THE TOP OF THE |
| GUARDRAIL, A CONCENTRATED HORIZONTAL |
| LOAD OF 200 LB APPLIED ON A 1 SQ FT AREA |
| AT ANY POINT, AND A LINE LOAD OF 50 PLF |
| APPLIED HORIZONTALLY AT THE REQUIRED |
| GUARDRAIL HEIGHT WITH A SIMULTANEOUS |
| LINE LOAD OF 100 PLF APPLIED VERTICALLY |
| DOWNWARD ON THE TOP OF THE GUARDRAIL. |
| THESE LOADS SHALL NOT BE APPLIED |
| SIMULTANEOUSLY (UNLESS NOTED ABOVE) BUT |
| SHALL BE APPLIED INDIVIDUALLY TO PRODUCE |
| MAXIMUM STRESS IN EACH OF THE COMPONENTS |
| OR SUPPORTS.AMEND/ANNOTATE THE PLANS. |
| |
| 29) FL. ADMIN CODE RULE 9B-72. |
| A SEARCH AT THE DEPT OF COMMUNITY |
| AFFAIRS PRODUCT APPROVAL WEBSITE |
| WWW.FLORIDABUILDING.ORG/PR/PR_SRCH.ASP |
| SHOWS NO MATCHING STATEWIDE PRODUCT |
| APPROVAL FOR THE SUBMITTED JOHNS |
| MANVILLE MODIFIED BITUMEN ROOFING SYSTEM |
| (FOR CONCRETE DECK) PRODUCT APPROVAL |
| NOA# 01-0206.19 OR THE SOLAROLL ROLLING |
| SHUTTER PRODUCT APPROVAL NOA# 02-0426.04 |
| SPECIFY ALTERNATIVES THAT HAVE |
| STATEWIDE OR LOCAL PRODUCT APPROVAL. |
| |
| 30) PRODUCT APPROVAL.RULE 9B-72 FAC. |
| FOR PRODUCTS WHICH DO NOT HAVE STATEWIDE |
| PRODUCT APPROVAL, LOCAL PRODUCT APPROVAL |
| CAN BE ACHIEVED IF THERE IS A QUALITY |
| ASSURANCE PROGRAM IN PLACE WITH A STATE |
| APPROVED QUALITY ASSURANCE ENTITY.IF |
| NEITHER IS APPLICABLE, THEN SITE |
| SPECIFIC APPROVAL IS REQUIRED.LOCAL |
| PRODUCT APPROVAL WILL ALLOW A PRODUCT TO |
| BE USED, IN ACCORDANCE WITH THE TEST |
| CRITERIA, THROUGHOUT THE JURISDICTION OF |
| WEST PALM BEACH.SITE SPECIFIC PRODUCT |
| APPROVAL WILL ALLOW A PRODUCT TO BE |
| USED ONLY ON THE PROJECT FOR WHICH THAT |
| SITE SPECIFIC APPROVAL IS GRANTED. |
| LOCAL AND SITE SPECIFIC PRODUCT APPROVAL |
| APPLICATION FORMS ARE AVAILABLE FROM |
| THIS OFFICE.APPROVED QUALITY ASSURANCE |
| ENTITIES ARE LISTED ON THE DCA WEBSITE: |
| WWW.FLORIDABUILDING.ORG/COMMON/C_ORG_ |
| REGI_SRCH.ASP |
| |
| 31) THE SUBMITTAL OF PRODUCT APPROVALS |
| FOR THE ROOF TILE, SKYLIGHT, EXTERIOR |
| DOORS, STOREFRONT AND WINDOWS IS NOTED. |
| THE APPROPRIATE STATEWIDE PRODUCT |
| APPROVAL LISTING HAS BEEN ATTACHED TO |
| EACH ONE.NOTE THAT PRODUCT APPROVALS |
| ARE NOW REQUIRED TO BE SUBMITTED LIKE |
| THIS.ALSO THREE COPIES (SEE COMMENT |
| BELOW ABOUT THRESHOLD BUILDING) OF ALL |
| PRODUCT APPROVALS ARE REQUIRED.SUBMIT |
| TWO FURTHER COPIES OF THE PRODUCT |
| APPROVALS COMPLETE WITH THE STATEWIDE |
| PRODUCT APPROVAL COVER SHEETS. |
| |
| 32) SKYLIGHT PRODUCT APPROVAL.THE |
| STATEWIDE PRODUCT APPROVAL LISTING FOR |
| THE SUBMITTED MIAMI-DADE NATURALITE |
| ALUMINUM SKYLIGHT PRODUCT APPROVAL |
| NOA# 01-0118.02 STATES A SIZE LIMITATION |
| OF 7'-0"X 8'-0".THIS SIZE IS EXCEEDED |
| BY THAT SPECIFIED ON SHEET A1.4.SUBMIT |
| AN ALTERNATIVE PRODUCT APPROVAL. |
| |
| 33) SUBMIT PRODUCT APPROVALS FOR THE |
| FIXED TRANSOM (AND HORIZONTAL MULLION) |
| OVER THE CASEMENT WINDOW TYPE C1 AND |
| FOR THE EXTERIOR DOORS 1-001-1, 1-207-1 |
| AND 1-307-1 WHICH ARE NOT COVERED BY THE |
| STOREFRONT PRODUCT APPROVAL. |
| NOTE: FL. ADMIN CODE RULE 9B-72 (IN |
| EFFECT SINCE OCTOBER 1, 2003) REQUIRES |
| THAT PRODUCTS HAVE STATEWIDE, LOCAL OR |
| SITE-SPECIFIC PRODUCT APPROVAL.THE |
| SUBMITTAL SHOULD INCLUDE THE STATEWIDE |
| PRODUCT APPROVAL NUMBER (FL###), |
| AVAILABLE FROM THE DEPT OF COMMUNITY |
| AFFAIRS PRODUCT APPROVAL WEBSITE |
| WWW.FLORIDABUILDING.ORG/PR/PR_SRCH.ASP |
| |
| 34) FBC* 105.13.1SPECIAL INSPECTOR.A |
| STRUCTURAL INSPECTION PLAN MUST BE |
| SUBMITTED PRIOR TO THE ISSUANCE OF A |
| BUILDING PERMIT FOR THE CONSTRUCTION OF |
| A THRESHOLD BUILDING.A THRESHOLD |
| BUILDING IS ANY BUILDING WHICH IS |
| GREATER THAN THREE STORIES OR 50 FEET IN |
| HEIGHT, OR WHICH HAS AN ASSEMBLY |
| OCCUPANCY WITH 5,000 SQFT AREA AND |
| GREATER THAN 500 OCCUPANTS.THREE |
| COPIES OF THE PLANS AND OTHER DOCUMENTS |
| WILL BE REQUIRED FOR PERMITTING PURPOSES |
| |
| 35) THE OLD SHEETS SHALL BE REMOVED FROM |
| THE CURRENT PLAN SETS.ONE SET OF THE |
| OLD SHEETS SHOULD SUBMITTED SEPARATELY |
| AS FOLLOWS: |
| TO EXPEDITE REVIEW OF A RESUBMITTAL |
| WHICH REQUIRES NEW PLANS IN ORDER TO |
| ADDRESS THE ABOVE COMMENTS, THE OLD |
| SHEETS SHALL BE REMOVED AND THE NEW |
| SHEETS INSERTED.ONE COPY OF EACH OLD |
| SHEET SHOULD BE STAPLED/CLIPPED TO THE |
| REMAINING OLD SHEETS FOR COMPARISON OF |
| REVISIONS WHEN REVIEWING THE RESUBMITTED |
| PLANS. |
| |
| **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| |
| END OF REVIEW COMMENTS |