Plan Review Notes
Plan Review Notes For Permit 04040562
Permit Number 04040562
Review Stop E
Sequence Number 17
Notes
Date Text
2007-04-26 10:28:44** UNSAT **
  
 1) NOTE: PLEASE SEE RISER WHICH INDICATES A 150AMP OVER
 CURRENT PROTECTION ON THE HE PANEL WHICH IS 100A RATED.
 PLEASE SEE THAT THE FEEDERS WOULD NOT OF SUFFICIENT
 SIZE FOR THE 150AMPS.
 240.4, 310.16.
 ONLY NEED TO REVISE POSSIBLY 6.1 AND 7.1
 PLEASE ADJUST AND REVISED.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  