Plan Review Notes For Permit 04040562 |
Permit Number |
04040562 |
|
Review Stop |
E |
Sequence Number |
17 |
|
Notes |
Date |
Text |
2007-04-26 10:28:44 | ** UNSAT ** | | | | 1) NOTE: PLEASE SEE RISER WHICH INDICATES A 150AMP OVER | | CURRENT PROTECTION ON THE HE PANEL WHICH IS 100A RATED. | | PLEASE SEE THAT THE FEEDERS WOULD NOT OF SUFFICIENT | | SIZE FOR THE 150AMPS. | | 240.4, 310.16. | | ONLY NEED TO REVISE POSSIBLY 6.1 AND 7.1 | | PLEASE ADJUST AND REVISED. | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | REVIEWER. | | | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|