Plan Review Notes For Permit 04040562 |
Permit Number |
04040562 |
|
Review Stop |
M |
Sequence Number |
12 |
|
Notes |
Date |
Text |
2007-02-12 09:05:00 | ----------------DENIED----------------- | | | | 1. EF 1 RISER HAS BEEN DELETED FROM PLAN. NO PROVISION | | HAS BEEN MADE FOR DISCHARGE OF EXHAUST FROM FIRST FLOOR | | BATHROOMS. PLEASE CLARIFY. PERHAPS A REVISED PAGE M2.1 | | IS NEEDED OR MISSING FROM THIS SUBMITTAL. | | | | 2. PLEASE PROVIDE A RISER DETAIL SHOWING COMPLIANCE | | WITH 607.1.3 FIRE DAMPER EXCEPTIONS. PLEASE NOTE: | | EXCEPTION #2 APPLIES TO RETURN RISERS AND A CONSTANT | | UPWARD AIRFLOW IS NEEDED. | | | | 3. PG M-0.1NOTE (U) STATES THAT ABOVE CEILING AREAS | | ARE TO BE USED AS RETURN AIR PLENUMS. EXHAUST DUCTS | | UNDER POSITIVE PRESSURE SHALL NOT EXTEND INTO OR PASS | | THROUGH A PLENUM PER FBC,M 601.3. BY DELETING THE | | ROOFTOP FANS AND USING CEILING MOUNTED FANS, THE | | EXHAUST DUCTS ABOVE CEILING HAVE GONE FROM NEGATIVE | | PRESSURE TO POSITIVE PRESSURE AND SHALL NOT BE LOCATED | | IN A PLENUM. | | | | REVIEWED BY: | | RONALD J REGUEIRO | | 561-805-6719 | | [email protected] |
|