Plan Review Notes
Plan Review Notes For Permit 04040562
Permit Number 04040562
Review Stop P
Sequence Number 1
Notes
Date Text
2004-04-26 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FBC-2001 BUILDING
  
 1) SHT A4.3 SUBMIT DETAILS FOR SECTIONS
 11-4.16, 11-4.19, 11-4.22 AND 11-4.24
 AND ALL SUBSECTIONS.
 2) SHTS P-2.2 & P-2.3 SANT. RISER #2 AND
 WATER RISER #1 SHOWN AS SAME RISER.
 PLEASE CLARIFY.
 3) SHTS P-2.1 & P-2.3 (SANT. RISER DIAG-
 RAM) - FLOOR DRAIN IN DUMPSTER PAD NOT
 APPROVED. - STORM WATER SHALL NOT DRAIN
 INTO SANITARY.
 4) SHT P-3.2 WATER RISER DIAGRAM. PIPE
 SHOWN AS 4" @ 4% THRU 4" @ 1% NOT APPRO-
 VED. - HORIZONTAL DRAINAGE PIPING SHALL
 BE INSTALLED IN UNIFORM ALIGNMENT AT
 UNIFORM SLOPES. SECTION 704.1 - PIPE
 SHALL BE MINIMUM 5" PIPE @ 1% PER TABLE
 1106.3.
 5) SEPARATE GAS PERMIT REQUIRED. THE
 FOLLOWING INFORMATION IS REQUIRED FOR
 GAS PERMIT.
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES.
 C. TYPE OF GAS, (LP OR NATURAL)
 D. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 6) SHTS A1.4 & A1.4.1 INDICATE SIZE OF
 OVERFLOW SCUPPERS. SHOW WIDTH OF OPENING
 ON DETAIL #12
 7) SEPARATE IRRIGATION PERMIT/PLANS REQ-
 UIRED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]