Date |
Text |
2004-04-26 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 FUEL GAS |
| FBC-2001 CHAPTER 1 |
| FBC-2001 CHAPTER 11 |
| FBC-2001 BUILDING |
| |
| 1) SHT A4.3 SUBMIT DETAILS FOR SECTIONS |
| 11-4.16, 11-4.19, 11-4.22 AND 11-4.24 |
| AND ALL SUBSECTIONS. |
| 2) SHTS P-2.2 & P-2.3 SANT. RISER #2 AND |
| WATER RISER #1 SHOWN AS SAME RISER. |
| PLEASE CLARIFY. |
| 3) SHTS P-2.1 & P-2.3 (SANT. RISER DIAG- |
| RAM) - FLOOR DRAIN IN DUMPSTER PAD NOT |
| APPROVED. - STORM WATER SHALL NOT DRAIN |
| INTO SANITARY. |
| 4) SHT P-3.2 WATER RISER DIAGRAM. PIPE |
| SHOWN AS 4" @ 4% THRU 4" @ 1% NOT APPRO- |
| VED. - HORIZONTAL DRAINAGE PIPING SHALL |
| BE INSTALLED IN UNIFORM ALIGNMENT AT |
| UNIFORM SLOPES. SECTION 704.1 - PIPE |
| SHALL BE MINIMUM 5" PIPE @ 1% PER TABLE |
| 1106.3. |
| 5) SEPARATE GAS PERMIT REQUIRED. THE |
| FOLLOWING INFORMATION IS REQUIRED FOR |
| GAS PERMIT. |
| A. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2001 |
| FUEL GAS CODE. |
| B. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES. |
| C. TYPE OF GAS, (LP OR NATURAL) |
| D. INDICATE THE DELIVERY PRESSURE (PSI) |
| PER FBC-2001 FUEL GAS CODE SEC. 402.2. |
| NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2001 FUEL GAS CODE SEC 402.2 |
| 6) SHTS A1.4 & A1.4.1 INDICATE SIZE OF |
| OVERFLOW SCUPPERS. SHOW WIDTH OF OPENING |
| ON DETAIL #12 |
| 7) SEPARATE IRRIGATION PERMIT/PLANS REQ- |
| UIRED. |
| |