Plan Review Notes For Permit 04040562 |
Permit Number |
04040562 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-04-16 00:00:00 | DENIED: | | 1.PLAN SHEET A3.2 DETAIL 01, INDICATES | | HVAC CHASE WITH FIRE DAMPER.PLEASE | | INDICATE SHAFT ON MECHANICAL PLAN.PER | | 2001 FBC(M) 607.6, SPECIFIC LOCATION OF | | EACH FIRE DAMPER, FIRE DOOR & CEILING | | DAMPER.IDENTIFY FIRE DAMPERS ON THE | | MECHANICAL PLAN. | | | | 2.DUCT SMOKE DETECTORS REQUIRED PER | | 2001 FBC(M) 606.2.1.(NOT SHOWN ON THE | | MECHANICAL PLAN) | | | | 3.NO COMBUSTIBLES ABOVE THE CEILING | | IN THE RETURN AIR PLENUM. | | | | 4.PLEASE CLARIFY THE PURPOSE OF THE | | BARAMETRIC RELIEF SHOWN ON FLOORS 1-4. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|