2004-04-16 00:00:00DENIED:
 1.PLAN SHEET A3.2 DETAIL 01, INDICATES
 HVAC CHASE WITH FIRE DAMPER.PLEASE
 INDICATE SHAFT ON MECHANICAL PLAN.PER
 2001 FBC(M) 607.6, SPECIFIC LOCATION OF
 EACH FIRE DAMPER, FIRE DOOR & CEILING
 DAMPER.IDENTIFY FIRE DAMPERS ON THE
 MECHANICAL PLAN.
  
 2.DUCT SMOKE DETECTORS REQUIRED PER
 2001 FBC(M) 606.2.1.(NOT SHOWN ON THE
 MECHANICAL PLAN)
  
 3.NO COMBUSTIBLES ABOVE THE CEILING
 IN THE RETURN AIR PLENUM.
  
 4.PLEASE CLARIFY THE PURPOSE OF THE
 BARAMETRIC RELIEF SHOWN ON FLOORS 1-4.
  