2004-05-11 00:00:00FAILED:
 1. SURVEYING SHEET MUST HAVE THE
 ORIGINAL RAISED SEAL AND SIGNATURE OF
 THE REGISTERED LAND SURVEYOR.
 2. CIVIL PLANS MUST BE APPROVED FOR ALL
 THE CONNECTION TO THE CITY SERVICES BY
 THE PUBLIC UTILITIES & ENGINEERING, ATT:
 MANNY GONZALEZ, 659-8040.
 3. WATER MAIN WITHIN PUBLIC R.O.W MUST
 BE DIP, AND PER CITY SPECIFICATION.
 4. SEPARATION/ CLEARANCE AT CONFLICT
 POINT BETWEEN PIPES MUST BE PER CITY OF
 WPB STANDARD, P-1.
 5. RECOMMENDED TO LOCATE THE FDC IN THE
 PROPOSED PLANTER AREA, PLEASE VERIFY.
 6. SITE FOR ALL NEW COMMERCIAL BUILDING
 MUST BE DESIGNED PER CITY OF WPB
 CRITERIA FOR STORM WATER.
 7. M.O.T PLAN MUST BE SUBMITTED TO THE
 PUBLIC UTILITIES & ENGINEERING FOR THEIR
 APPROVAL FOR ANY CONSTRUCTION WITHIN
 R.O.W PRIOR TO ANY CONSTRUCTION BEGINS.
 8. SUBMIT PERVIOUS AND IMPERVIOUS AREA
 FOR ENTIRE SITE.
 9. COVER FOR PUBLIC STORM WATER MANHOLE
 MUST HAVE CITY' LOGO.
 10. PLEASE SHOW WHERE THE ST2-2, ST-2-3,
 ST-2-1 AS DETAILED ON SHEET C-4 ARE
 GOING TO BE USED.
 11. CITY STANDARDS MAY BE OBTAIN FROM
 PUBLIC UTILITIES AND ENGINEERING.
 12. PLEASE NOTE THAT THE PROPOSED SITE
 HAS NOT BEEN APPROVED BY PLANNING AND
 ZONING.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI