2004-04-22 00:00:00 | ************** UNSAT **************** |
| |
| 1)NOTE: PLEASE SEE 700.16 FOR REQ'D |
| LTS FOR ROOMS/STAIRS ETC. PLEASE SEE |
| FIRE REVIEW COMMENTS. |
| STAIR LTS ARE SHOWN ON HOUSE PANEL WHICH |
| ARE ON GEN YET, THESE ARE ALSO SHOWN |
| AS BATTERY BACK UP? |
| |
| 2)NOTE: PLEASE SEE BLDG/STRUCTUAL PLANS, |
| THESE INDICATE NO SPACE IN BETWEEN |
| EXISTING BLDGS AND NEW. PLEASE SEE |
| ELECTRICAL PLANS, THESE SHOW NEW HOUSE |
| PANELS AND ATS ON EAST WALL. PLEASE |
| CLARIFY HOW THIS IS GOING TO WORK? |
| 110.26 ETC. |
| |
| 3)NOTE: PLEASE SEE 250.32 AND 225.31 |
| FOR GROUNDING AND MEANS OF DISCONNECT |
| AT DETACHED STRUCTURE./ ATM BLDG. |
| |
| 4)NOTE: PLEASE PROVIDE MORE INFORMATION |
| ON FIRE PUMP/GENERATOR/ ATS ETC. |
| MUST MEET 695.4B1, 230.76,230.79 ETC |
| THERE IS NO INDICATION OF DISC MEANS |
| FROM GENERATOR? |
| PLEASE ALSO SUBMIT SPEC SHEETS FOR GEN/ |
| ETC. |
| |
| 5)NOTE: PLEASE ALSO SHOW DISC MEANS FOR |
| POWER TO HOUSE PANEL/ATS. THIS IS SHOWN |
| AS A MLO PANEL. PLEASE ALSO SEE GROUPING |
| PER 230.72. |
| |
| 6)NOTE: PLEASE PROVIDE ROOM DESIGNATIONS |
| ON ELECTRICAL PLANS. |
| |
| 7)NOTE: PLEASE SEE 250.6/250.24 NO, |
| EQUIPMENT GROUNDING CONDUCTORS INSTALLED |
| FROM METER TO MAINS. |
| |
| 8)NOTE: PLEASE SUBMIT FPL INFORMATION |
| FOR SIZE OF TRANSFORMER/ IMPEDENCE ETC. |
| IT IS NOTED THAT AIC CALCS ARE SHOWN. |
| |
| PLEASE NOTE; DUE TO SOME CHANGES THAT |
| WILL NEED TO BE CHANGED ON PLANS, THERE |
| MAY OR MAY NOT BE OTHER COMMENTS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |
| 561-805-6717 |
| [email protected] |