2004-05-13 00:00:00 | BUILDING PLAN REVIEW |
| *******DENIED******* |
| ROBERT BROWN(561) 805 6716 |
| E-MAIL: [email protected] |
| |
| FBC = FLORIDA BUILDING CODE 2001 |
| FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| |
| 1) THE NOTICE OF COMMENCEMENT SHALL BE |
| RECORDED AT PALM BEACH COUNTY COURTHOUSE |
| AND A COPY SUBMITTED TO THIS OFFICE |
| BEFORE A PERMIT CAN BE ISSUED.BLANK |
| FORMS ARE AVAILABLE FROM THIS OFFICE. |
| |
| 2) IMPACT FEES. THE PLANS SHALL BE TAKEN |
| TO PALM BEACH COUNTY BUILDING DEPARTMENT |
| FOR IMPACT FEE ASSESSMENT. THEY SHALL BE |
| STAMPED AT THAT OFFICE AND A COPY OF THE |
| PAID RECEIPT SUBMITTED TO THE CITY OF |
| WEST PALM BEACH DEPT OF CONSTRUCTION |
| SERVICES BEFORE A PERMIT CAN BE ISSUED. |
| |
| 3) FBC* 104.6.5BUILDING PERMIT |
| VALUATION.THE STATED VALUE OF THE |
| PROJECT HAS BEEN UNDER-ESTIMATED AT |
| $1,200,000.THE VALUE CALCULATED USING |
| THE SOUTHERN BUILDING CODE CONGRESS |
| INTERNATIONAL (SBCCI) VALUATION TABLES |
| IS $1,586,125.THE PERMIT APPLICATION |
| FEE HAS BEEN ADJUSTED ACCORDINGLY.THE |
| OUTSTANDING BALANCE MUST BE PAID BEFORE |
| A PERMIT CAN BE ISSUED. |
| |
| 4) FBC* 104.1.5BUILDING ADDRESS. THE |
| PROJECT TITLE SHEET STATES THE ADDRESS |
| OF THE PROPOSED BUILDING AS |
| 307 EVERNIA STREET.AMEND SHEET A0.1 TO |
| SHOW THE FRONT ENTRANCE LOCATION AND |
| ADDRESS FOR THE ADJACENT EXISTING |
| 3-STORY AND 5-STORY OFFICE BUILDINGS SO |
| VALIDITY OF THE PROPOSED ADDRESS CAN BE |
| VERIFIED.ALSO, EVERY DRAWING SHEET |
| REFERS TO '310 EVERNIA STREET' WHICH IS |
| NOT THE CORRECT ADDRESS.AMEND THE |
| SHEETS. |
| |
| 5) FBC* 104.2.4SITE SURVEY.THE |
| SUBMITTED SURVEY DRAWING IS NOT SIGNED |
| AND SEALED.ALSO, IT DOES NOT REFLECT |
| THE OUTLINE OF THE EXISTING OFFICE |
| BUILDINGS THAT WILL REMAIN, SO THAT THE |
| DIMENSIONS OF THE SPACE AVAILABLE FOR |
| THE NEW BUILDING MAY BE DETERMINED. |
| SHEETS A0.1 AND LS1.1 STATE BUILDING |
| DIMENSIONS THAT EXCEED THE AVAILABLE |
| SPACE AS SHOWN ON THE SUBMITTED SURVEY. |
| SUBMIT A SIGNED AND SEALED SURVEY |
| DRAWING PREPARED BY A LICENSED SURVEYOR/ |
| MAPPER IS REQUIRED (REF: 472.025(1) F.S) |
| AND ENSURE THAT THE PROPOSED BUILDING |
| WILL FIT IN THE AVAILABLE SPACE. |
| |
| 6) FBC* 1804.2.2GEOTECHNICAL REPORT. |
| SHEET S1.1, FOUNDATION PLAN NOTE 2 |
| REFERS TO A 2/18/2004 TIERA INC. |
| GEOTECHNICAL REPORT NO 6611-04-032. |
| SUBMIT THE GEOTECHNICAL REPORT TO VERIFY |
| THE SAFE BEARING CAPACITY OF THE SOIL. |
| |
| 7) FBC 13-103.0ENERGY CODE COMPLIANCE |
| SHALL BE DEMONSTRATED BY SUBMITTAL OF |
| APPROPRIATE CODE COMPLIANCE FORMS |
| |
| 8) 61G15-23.002(2)FL. ADMIN. CODE. |
| SHEETS C-1 TO C-4 SHALL INCLUDE THE |
| ADDRESS OF ANTHONY J. MICHUDA, P.E (THIS |
| INFORMATION MAY BE HANDWRITTEN/STAMPED |
| ON EACH COPY SUBMITTED FOR PERMITTING) |
| TO COMPLY WITH THE FOLLOWING: |
| PLANS SIGNED & SEALED BY A PROFESSIONAL |
| ENGINEER SHALL INCLUDE EITHER THE NAME, |
| ADDRESS AND LICENSE NUMBER OF THE |
| ENGINEER OR, THE NAME AND LICENSE NUMBER |
| OF THE ENGINEER AND THE NAME, ADDRESS |
| AND CERTIFICATE OF AUTHORIZATION NUMBER |
| OF THE ENGINEERING BUSINESS THROUGH |
| WHICH THE ENGINEER IS PRACTICING |
| (471.025 F.S. AND 471.023 F.S.). |
| |
| 9) FBC TABLE 600SURVEY DRAWING AND |
| SHEETS LS1.1 AND A1.1.WHAT IS THE |
| WIDTH OF THE REAR ALLEY USED TO |
| DETERMINE THE HORIZONTAL SEPARATION AND |
| PROTECTION OF OPENINGS?AMEND THE |
| PLANS TO CLARIFY. |
| |
| 10) FBC 1006.1.4SHEET A4.2, STAIR #1 - |
| PARTIAL SECTION (DETAIL 06).THE CLOSET |
| (AND COUPON ROOM) UNDER THE STAIR SHALL |
| BE SEPARATED FROM THE STAIR BY A MINIMUM |
| OF 2 HOUR FIRE RESISTANT CONSTRUCTION. |
| AMEND/ANNOTATE THE PLANS TO DEMONSTRATE |
| COMPLIANCE. |
| |
| 11) FBC 1006.2.2EXTERIOR EXIT STAIR. |
| AMEND SHEETS LS1.2 AND A1.2 TO SHOW ALL |
| OPENINGS IN THE WALLS OF THE ADJACENT |
| 3-STORY AND 5-STORY OFFICE BUILDINGS |
| WITHIN 10 FEET OF THE EXTERIOR EXIT |
| STAIR AND LANDING.ANY SUCH OPENINGS |
| MUST HAVE 3/4 HOUR FIRE RESISTANT DOORS |
| AND WINDOWS.AMEND THE PLANS TO VERIFY |
| THIS.DO EITHER OF THE ADJACENT |
| BUILDINGS HAVE EXITS LEADING TO THIS |
| EXTERIOR EXIT STAIR?AMEND THE PLANS TO |
| CLARIFY. |
| |
| 12) FBC 1007SHEET A4.1, STAIR PLANS. |
| STAIR #2 SECOND FLOOR PLAN.NO WIDTH |
| DIMENSION OR HANDRAIL ARE SHOWN FOR THE |
| EXISTING STAIR BEING PROPOSED AS THE |
| FIRST FLOOR FLIGHT FOR STAIR #2.WHAT |
| ARE THE TREAD AND RISER DIMENSIONS FOR |
| THIS STAIR FLIGHT?AMEND THE PLANS TO |
| DEMONSTRATE FULL COMPLIANCE FOR THIS |
| PORTION OF STAIR #2. |
| |
| 13) FBC 1007.4SHEET A4.1, STAIR PLANS. |
| THE STAIR #1 FOURTH FLOOR PLAN DOES NOT |
| REFLECT THE LANDING ARRANGEMENT SHOW ON |
| SHEETS LS1.3 AND A1.3.AMEND THE DETAIL |
| ALSO, THE STAIR #1 SECOND FLOOR PLAN |
| SHOWS 14 RISERS FOR THE FIRST FLIGHT |
| DOWN TO FIRST FLOOR.SHOULD THIS NOT |
| READ 7 RISERS INSTEAD OF 14? |
| |
| 14) SHEET S2.4STAIR SUPPORT.IS THE |
| MC12 STAIR STRINGER TO BE BUILT INTO |
| EACH CMU WALL?PROVIDE A TITLE FOR THE |
| 'CONCRETE PAD' DETAIL OR ANNOTATE IT AS |
| 'TYPICAL' TO CLARIFY WHERE IT APPLIES. |
| |
| 15) FBC 1608.2.1SHEET A4.2, STAIR |
| HANDRAIL DETAILS.THE HANDRAIL SHALL BE |
| DESIGNED AND CONSTRUCTED FOR A |
| CONCENTRATED LOAD OF 200 LB AND A LINE |
| LOAD OF 50 PLF.THESE LOADS SHALL NOT |
| BE APPLIED SIMULTANEOUSLY BUT SHALL BE |
| APPLIED INDIVIDUALLY AT ANY POINT, AND |
| IN ANY DIRECTION, TO PRODUCE MAXIMUM |
| STRESS IN EACH OF THE COMPONENTS OR |
| SUPPORTS.AMEND/ANNOTATE THE PLANS. |
| |
| 16) FBC 1608.2.2SHEETS A4.2 AND A4.5, |
| STAIR GUARDRAIL DETAILS AND BALCONY |
| GUARDRAILS.THE GUARDRAILS SHALL BE |
| DESIGNED AND CONSTRUCTED FOR A |
| CONCENTRATED LOAD OF 200 LB APPLIED IN |
| ANY DIRECTION AT THE TOP OF THE |
| GUARDRAIL, A CONCENTRATED HORIZONTAL |
| LOAD OF 200 LB APPLIED ON A 1 SQ FT AREA |
| AT ANY POINT, AND A LINE LOAD OF 50 PLF |
| APPLIED HORIZONTALLY AT THE REQUIRED |
| GUARDRAIL HEIGHT WITH A SIMULTANEOUS |
| LINE LOAD OF 100 PLF APPLIED VERTICALLY |
| DOWNWARD ON THE TOP OF THE GUARDRAIL. |
| THESE LOADS SHALL NOT BE APPLIED |
| SIMULTANEOUSLY (UNLESS NOTED ABOVE) BUT |
| SHALL BE APPLIED INDIVIDUALLY TO PRODUCE |
| MAXIMUM STRESS IN EACH OF THE COMPONENTS |
| OR SUPPORTS.AMEND/ANNOTATE THE PLANS. |
| |
| 17) FBC 11-4.9.4SHEET A4.1, STAIR |
| PLANS.THE STAIR #2 SECOND FLOOR PLAN |
| DOES NOT SHOW THE REQUIRED HANDRAIL |
| EXTENSION AGAINST THE EXTERIOR WALL AT |
| THE BOTTOM OF THE FLIGHT. |
| |
| 18) FBC 11-4.16 SHEET A4.3, WATER CLOSET |
| ACCESSIBILTY DIMENSIONS.THE SEAT AND |
| SIDE GRAB BAR HEIGHTS ARE LOWER THAN |
| THE ALLOWABLE RANGE GIVEN IN THE CODE. |
| ALSO, WILL THE PROPOSED HEIGHT OF THE |
| DRINKING FOUNTAIN AND LAVATORIES PROVIDE |
| THE REQUIRED MINIMUM LEG/KNEE CLEARANCE? |
| AMEND THE DETAILS. |
| |
| 19) FBC 11-4.13.6SHEET A1.1, FIRST |
| FLOOR PLAN.THE DOOR TO THE BREAK ROOM |
| (1-114) SHALL HAVE A MANEUVERING |
| CLEARANCE OF AT LEAST 12", ON THE PUSH |
| SIDE, BETWEEN THE ADJACENT WALL AND THE |
| STRIKE EDGE OF THE DOOR, IF THE DOOR HAS |
| BOTH A CLOSER AND A LATCH (FIG. 25). |
| ANNOTATE THE PLANS TO DEMONSTRATE |
| COMPLIANCE. |
| |
| 20) FBC 1606.1.4HURRICANE MISSILE |
| IMPACT PROTECTION.SHEET A6.1, DOOR |
| SCHEDULE, STATES THAT ONLY DOOR 1-104-1 |
| HAS IMPACT RESISTANT GLAZING.THAT DOOR |
| IS SHOWN AS AN INTERIOR DOOR (TO TELLER |
| OFFICE) ON SHEET A1.1 AND IS A TYPE F |
| DOOR (SHEET A6.1.1) WHICH DOES NOT HAVE |
| ANY GLAZING. AMEND THE DOOR SCHEDULE TO |
| SPECIFY THE REQUIRED IMPACT RESISTANCE |
| FOR DOOR 1-001-1. |
| |
| 21) FBC 1606.1.4HURRICANE MISSILE |
| IMPACT PROTECTION.SHEET A6.1.1, THE |
| WINDOW DETAILS DO NOT SPECIFY THE |
| REQUIRED IMPACT RESISTANCE FOR THE |
| WINDOWS.AMEND THE PLANS. |
| |
| 22) FBC 2405.2THE FOLLOWING GLAZING IS |
| IN A 'HAZARDOUS LOCATION' AND IS |
| REQUIRED TO BE SAFETY GLASS SATISFYING |
| THE REQUIREMENTS OF THE CONSUMER PRODUCT |
| SAFETY COMMISSION 16, CODE OF FEDERAL |
| REGULATIONS, PART 1201 (CPSC 16-CFR, |
| PART 1201): |
| - GLAZING ADJACENT TO THE FIRST FLOOR |
| DOORS AT THE LOBBY, CONFERENCE ROOM |
| (1-108), TELLER OFFICE (1-104) AND |
| OFFICE (1-103). |
| - GLAZING IN THE DOORS. |
| SUBMIT DETAILS TO DEMONSTRATE COMPLIANCE |
| |
| 23) FBC 2407.3SHEET A1.4, SKYLIGHTS. |
| AMEND THE PLANS TO STATE WHICH TYPE OF |
| "SAFETY GLASS" IS TO BE USED.IF HEAT |
| STRENGTHENED OR FULLY TEMPERED GLASS ARE |
| USED, PROTECTIVE SCREENS SHALL BE |
| INSTALLED BELOW THE GLAZING, AS REQUIRED |
| BY FBC 2407.3, TO PROTECT THE BUILDING |
| OCCUPANTS FROM FALLING GLASS IN THE |
| EVENT OF BREAKAGE.AMEND THE DETAILS/ |
| ANNOTATION TO DEMONSTRATE COMPLIANCE. |
| |
| 24) FBC 3003.4.1STRETCHER ACCESSIBLE |
| ELEVATOR.AT LEAST ONE PASSENGER |
| ELEVATOR SHALL ACCOMMODATE AN AMBULANCE |
| STRETCHER 76" LONG AND 24" WIDE IN THE |
| HORIZONTAL POSITION.THIS ELEVATOR |
| SHALL BE IDENTIFIED BY SIGNAGE.AMEND |
| THE PLANS TO DEMONSTRATE COMPLIANCE. |
| |
| 25) FBC* F102.2.6SHEET LS1.1, CODE |
| SUMMARY - FIRE RESISTANCE RATING NOTES. |
| EXTERIOR WALLS OF TYPE IV BUILDINGS |
| LOCATED IN THE FIRE DISTRICT SHALL HAVE |
| A FIRE-RESISTANCE OF 2-HOURS OR MORE |
| IF LOCATED WITHIN 30 FEET OF A COMMON |
| PROPERTY LINE OR ASSUMED PROPERTY LINE. |
| AMEND THE NOTES AND ALL PLANS TO STATE |
| 2-HOUR FIRE RATING FOR THE EXTERIOR |
| WALLS. |
| |
| 26) FBC* F102.2.7ARCHITECTURAL TRIM IN |
| FIRE DISTRICT.SHEET A1.4.1 (DETAILS 01 |
| AND 02), SHEET A2.1 TO SHEET A2.4 |
| (EXTERIOR ELEVATIONS), SHEET A3.2 |
| (SECTIONS 01 AND 04), SHEET A3.2.1 |
| (DETAIL 01) AND SHEET A4.5 (DETAILS 01 |
| 02, 03, 06 AND 07) ALL REFER TO APPLIED |
| FOAM MOLDINGS.ARCHITECTURAL TRIM |
| TRIM ON BUILDINGS LOCATED IN THE FIRE |
| DISTRICT, SHALL BE CONSTRUCTED OF |
| APPROVED NON-COMBUSTIBLE MATERIALS OR |
| FIRE RETARDANT TREATED WOOD.AMEND THE |
| PLANS TO DEMONSTRATE COMPLIANCE. |
| |
| 27) FBC 1606.1.3SHEET S2.3, TRUSS |
| BEARING DETAIL.ADD A TRUSS ANCHOR |
| SCHEDULE/DETAIL, OR ADD NOTES STATING |
| THE CALCULATED TRUSS UPLIFTS AND THAT |
| THE METAL TRUSS MANUFACTURER WILL HAVE A |
| FLORIDA REGISTERED ENGINEER SPECIFY/ |
| DESIGN ANCHORS FOR FOR THOSE UPLIFTS. |
| |
| 28) FBC 1606.1.4HURRICANE MISSILE |
| IMPACT PROTECTION.ANNOTATE THE PLANS/ |
| SCHEDULES TO STATE THE PROPOSED MEANS OF |
| HURRICANE MISSILE IMPACT PROTECTION. |
| |
| 29) SUBMIT PRODUCT APPROVALS FOR THE |
| SKYLIGHTS, WINDOWS, MULLIONS, EXTERIOR |
| DOORS, ROOF TILE AND BUILT-UP ROOFING |
| SYSTEM.NOTE: FL. ADMIN CODE RULE 9B-72 |
| (IN EFFECT SINCE OCT' 1, 2003) REQUIRES |
| THAT PRODUCTS HAVE STATEWIDE, LOCAL OR |
| SITE-SPECIFIC PRODUCT APPROVAL.THE |
| SUBMITTAL SHOULD INCLUDE THE STATEWIDE |
| PRODUCT APPROVAL NUMBER (FL###), |
| AVAILABLE FROM THE DEPT OF COMMUNITY |
| AFFAIRS PRODUCT APPROVAL WEBSITE |
| WWW.FLORIDABUILDING.ORG/PR/PR_SRCH.ASP |
| |
| 30) PRODUCT APPROVAL.RULE 9B-72 FAC. |
| FOR PRODUCTS WHICH DO NOT HAVE STATEWIDE |
| PRODUCT APPROVAL, LOCAL PRODUCT APPROVAL |
| CAN BE ACHIEVED IF THERE IS A QUALITY |
| ASSURANCE PROGRAM IN PLACE WITH A STATE |
| APPROVED QUALITY ASSURANCE ENTITY.IF |
| NEITHER IS APPLICABLE, THEN SITE |
| SPECIFIC APPROVAL IS REQUIRED.LOCAL |
| PRODUCT APPROVAL WILL ALLOW A PRODUCT TO |
| BE USED, IN ACCORDANCE WITH THE TEST |
| CRITERIA, THROUGHOUT THE JURISDICTION OF |
| WEST PALM BEACH.SITE SPECIFIC PRODUCT |
| APPROVAL WILL ALLOW A PRODUCT TO BE |
| USED ONLY ON THE PROJECT FOR WHICH THAT |
| SITE SPECIFIC APPROVAL IS GRANTED. |
| LOCAL AND SITE SPECIFIC PRODUCT APPROVAL |
| APPLICATION FORMS ARE AVAILABLE FROM |
| THIS OFFICE.APPROVED QUALITY ASSURANCE |
| ENTITIES ARE LISTED ON THE DCA WEBSITE: |
| WWW.FLORIDABUILDING.ORG/COMMON/C_ORG_ |
| REGI_SRCH.ASP |
| |
| 31) TO EXPEDITE REVIEW OF A RESUBMITTAL |
| WHICH REQUIRES NEW PLANS IN ORDER TO |
| ADDRESS THE ABOVE COMMENTS, THE OLD |
| SHEETS SHALL BE REMOVED AND THE NEW |
| SHEETS INSERTED.ONE COPY OF EACH OLD |
| SHEET SHOULD BE STAPLED/CLIPPED TO THE |
| REMAINING OLD SHEETS FOR COMPARISON OF |
| REVISIONS WHEN REVIEWING THE RESUBMITTED |
| PLANS. |
| |
| **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| |
| END OF REVIEW COMMENTS |