2004-04-10 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
 1. TYPE OF GAS, (LP OR NATURAL)
 2. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 3. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2001 FUEL
 GAS CODE SECTION 304.
  