Plan Review Notes For Permit 04040457 |
Permit Number |
04040457 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-04-16 00:00:00 | ************** UNSAT *************** | | | | 1)NOTE: PLEASE CLARFIY , NOTE #1 MENTION | | SERVICE TO BE INSTALLED ABOVE 4'. | | IS THIS SERVICE NEW? | | IF SO PLEASE SUBMIT A COMPLETED RISER | | DIAGRAM. | | PANEL INDICATES BEING A 200A MLO PANEL. | | IS THERE AN EXSTING MAIN? OCP? | | | | 2)NOTE: PLEASE CORRELATE LOADS , PANEL | | SHOWS 114A'S AND EST LOAD CALCS SHOW | | 103A'S?? | | | | 3)NOTE: PLANS SHOWS WHAT APPEARS TO BE | | A NEW COND UNIT? OR IS THIS AN EXSITNG | | RELOCATION? | | PLEASE ALSO SEE OCP FOR AHU AND CU. | | PLEASE VERIFY. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] |
|