Plan Review Notes For Permit 04040247 |
Permit Number |
04040247 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-04-21 00:00:00 | DENIED | | REFERENCED: FBC-2001 PLUMBING | | FBC-2001 CHAPTER 1 | | | | 1) SHT P-105 A WATER HAMMER ARRESTOR IS | | REQUIRED AT THE REFRIG. PER SECTION | | 604.9 AT UNITS A, B, & C. NO WATER DROP | | SHOWN FOR REFRIG. IN B UNIT ON WATER | | RISER DIAGRAM. | | 2) SHT P-201 BUILDING 2 FLOOR PLAN. | | PLEASE CLARIFY THE PURPOSE FOR THIS | | SHEET. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|