2004-04-21 00:00:00DENIED
 REFERENCED: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SHT P-105 A WATER HAMMER ARRESTOR IS
 REQUIRED AT THE REFRIG. PER SECTION
 604.9 AT UNITS A, B, & C. NO WATER DROP
 SHOWN FOR REFRIG. IN B UNIT ON WATER
 RISER DIAGRAM.
 2) SHT P-201 BUILDING 2 FLOOR PLAN.
 PLEASE CLARIFY THE PURPOSE FOR THIS
 SHEET.
  