2004-04-20 00:00:00DENIED:
 1.PERMIT APPLICATION FOR LOT 151
 INDICATES AN "A" MODEL WHEREAS PLAN
 SHEET A1.01 REFLECTS A "C" MODEL. PLEASE
 CLARIFY.
  
 2.ENERGY CALCS FOR LOT 151 - CALCS
 INDICATE 1206 SQ FT CONDITIONED AREA &
 THE PLAN SHEET A3.03 & M-3 INDICATE
 1,343 UNDER A/C.PLEASE CORRECT.
  
 3.ENERGY CALCS EQUIPMENT SIZE DOES
 NOT MATCH EQUIPMENT SCHEDULE.PLEASE
 CORRECT.
  
 PLANS ARE OTHERWISE CODE COMPLIANT.
  
  
  