2004-06-03 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) FROM PREVIOUS REVIEW: #5 - SHT P-2
 WATER HEATER DETAIL. THERMAL EXPANSION
 CONTROL REQUIRED. SECTION 607.3.2
 2) SEE COMMENT #6 FROM PREVIOUS REVIEW.
 THE DATE THAT THE SIGNATURE AND SEAL IS
 AFFIXED SHALL BE ENTERED ON PLANS.
 FAC 61G15-23.002(1) & FS 471.025 - THIS
 IS REQUIRED ON ALL SHEETS.
 3) NEW COMMENT: SHT P-2 WATER RISER DIA-
 GRAM. AIR CHAMBERS ARE NOT APPROVED AND
 SHALL BE DELETED FROM RISER. WATER HAMM-
 ER ARRESTORS ARE REQUIRED AT THE DISH
 WASHER AND ICE MAKER IN REFRIG. PER SEC.
 604.9 AND LOCATED NEXT TO THE FIXTURE,
 NOT IN THE CEILING.
 4) NEW COMMENT: REMOVE ALL OLD/VOIDED
 SHEETS FROM PLANS. - SUBMIT ONE SET OF
 OLD/VOIDED SHEETS SEPARATE FROM SET FOR
 COMPAIRSON. SECTION 104.2.1
  
 REVIEW BY KEN STEVENS