2005-02-22 00:00:00********** NOTES REDLINED *********
  
 1)NOTE: PLEASE SEE CIRCUITING FOR SD'S,
 ALL ARE SHOWN ON MULTIPLE CIRCUITS,
 HOWEVER SD'S ARE REQUIRED TO BE WIRED
 "INLINE". MULTIPLE CIRCUITS WILL NOT
 WORK.
  
 2)NOTE: PLEASE CORRELATE LOADS FOR POOL
 PUMP AND HEAT. LOAD CALCS/ PANEL
 SCHEDULE LOAD.
  
  
  
  
 REVISE CIRCUTING AND PANEL SCHEDULE
 BEFORE FINAL.
  
 ALL OTHER REVISIONS TO BE SUBMITTED FOR
 REVIEW BEFORE ROUGH.
 CORRECT SD CIRCUTING AT THAT TIME.
  
 PLANS TO GO TO BLDG REVIEW ALSO, DUE TO
 HAND-DRAWN CHNAGES TO SIGNED AND SEALED
 PLANS.