2005-01-20 00:00:00 | DENIED |
| THIRD REVIEW FOR THESE SAME COMMENTS: |
| |
| 3. PRODUCT APPROVALS: |
| MISSING FOR ROOFING AND FIXED GLASS. |
| PLEASE SUBMIT 2 COPIES, WITH ATTACHED |
| STATE APPROVAL. |
| PC ALUMINUM DOOR HAS WRONG STATE |
| APPROVAL ATTACHED. |
| |
| 4. C) PERMIT VALUATION HAS BEEN REVISED |
| TO $650,000 AND ADDITIONAL PERMIT FEES |
| OF $7162.56 ARE DUE. |
| |
| 5. SHOW DETAILS FOR THE FOLLOWING: |
| |
| 1015.2 HEIGHT. GUARDRAILS SHALL |
| FORM A VERTICAL PROTECTIVE BARRIER NOT |
| LESS THAN 42" HIGH. |
| 1015.3 OPENINGS. OPEN GUARDRAILS |
| SHALL HAVE INTERMEDIATE RAILS OR ORNA- |
| MENTAL PATTERNS SUCH AS A 4" DIAMETER |
| SPHERE CAN NOT PASS THROUGH. A BOTTOM |
| RAIL OR CURB SHALL BE PROVIDED THAT |
| WILL |
| REJECT THE PASSAGE OF 2" DIAMETER |
| SPHERE. |
| |
| 7.SHOW ROOF DRAIN CALCULATIONS |
| INCLUDING SCUPPER SIZE HEIGHT OF |
| PARAPET |
| WALL AND SQUARE FOOT AREA IN EACH DRAIN |
| AREA. |
| |
| 10. SEE ELECTICAL NOTES #5 REGARDING |
| SMOKE DETECTORS.FBC 905.2 |
| |
| NEW COMMENT: |
| CHANGES MADE TO PLANS MUST BE SIGNED BY |
| THE DESIGNER OF RECORD. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT |
| NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR |
| SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE |
| FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| ART LANGE |
| BUILDING PLANS EXAMINER |
| 805-6672 |