2004-11-24 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SANITARY RISER DIAGRAM DOES NOT MEET
 CODE REQUIREMENTS, NOR DOES IT REFLECT
 THE FLOOR PLAN.
 A) THE WASH MACHINE REQUIRES A CLEANOUT
 4 FEET ABOVE THE FLOOR FOR ACCESS, AND A
 STANDPIPE. SECTIONS 708.10, & 1002.1
 B) THE FIRST FLOOR BATHROOM SHOWS THE
 TUB AND LAV ON THE SAME WALL AND THE LAV
 ON THE LEFT OF THE W/C ON THE RISER
 DIAGRAM, BUT ON THE FLOOR PLAN THE TUB
 AND LAV ARE ON DIFFERENT WALLS. SECTION
 104.2.1.
 C) THE FIRST FLOOR W/C SHALL NOT BE
 DOUBLE TRAPPED. SECTION 1002.1. THE W/C
 HAS AN INTEGRAL TRAP.
 D) TWO BIDETS SHOWN ON THE FLOOR PLAN
 ARE NOT SHOWN ON THE RISER DIAGRAM.
 SECTION 104.2.1
 E) ALL W/C'S SHALL NOT BE DOUBLE
 TRAPPED. SECTION 1002.1
 F) THE BATHROOM LAYOUTS ON THE RISER
 DIAGRAM DO NOT REFLECT THE FLOOR PLAN.
 SECTION 104.2.1
 G) NO HORIZONTAL DRY VENTS AS SHOWN
 PAST ALL THE SHOWERS ON THE SECOND FLOOR
 ON THE RISER DIAGRAM. SECTION 905.3.
 2) SEE RED LINE EXAMPLE OF A RISER
 DIAGRAM THAT REFLECTS THE FLOOR PLAN AND
 MEETS THE CODE REQUIREMENTS.
 3) ALL DRAWING SHALL BEAR THE NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR
 THE DOCUMENT. SECTION 104.2.1
  
  
  
  