2004-11-24 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 CHAPTER 1 |
| |
| 1) SANITARY RISER DIAGRAM DOES NOT MEET |
| CODE REQUIREMENTS, NOR DOES IT REFLECT |
| THE FLOOR PLAN. |
| A) THE WASH MACHINE REQUIRES A CLEANOUT |
| 4 FEET ABOVE THE FLOOR FOR ACCESS, AND A |
| STANDPIPE. SECTIONS 708.10, & 1002.1 |
| B) THE FIRST FLOOR BATHROOM SHOWS THE |
| TUB AND LAV ON THE SAME WALL AND THE LAV |
| ON THE LEFT OF THE W/C ON THE RISER |
| DIAGRAM, BUT ON THE FLOOR PLAN THE TUB |
| AND LAV ARE ON DIFFERENT WALLS. SECTION |
| 104.2.1. |
| C) THE FIRST FLOOR W/C SHALL NOT BE |
| DOUBLE TRAPPED. SECTION 1002.1. THE W/C |
| HAS AN INTEGRAL TRAP. |
| D) TWO BIDETS SHOWN ON THE FLOOR PLAN |
| ARE NOT SHOWN ON THE RISER DIAGRAM. |
| SECTION 104.2.1 |
| E) ALL W/C'S SHALL NOT BE DOUBLE |
| TRAPPED. SECTION 1002.1 |
| F) THE BATHROOM LAYOUTS ON THE RISER |
| DIAGRAM DO NOT REFLECT THE FLOOR PLAN. |
| SECTION 104.2.1 |
| G) NO HORIZONTAL DRY VENTS AS SHOWN |
| PAST ALL THE SHOWERS ON THE SECOND FLOOR |
| ON THE RISER DIAGRAM. SECTION 905.3. |
| 2) SEE RED LINE EXAMPLE OF A RISER |
| DIAGRAM THAT REFLECTS THE FLOOR PLAN AND |
| MEETS THE CODE REQUIREMENTS. |
| 3) ALL DRAWING SHALL BEAR THE NAME AND |
| SIGNATURE OF THE PERSON RESPONSIBLE FOR |
| THE DOCUMENT. SECTION 104.2.1 |
| |
| |
| |
| |