Date |
Text |
2004-11-17 00:00:00 | *********** UNSAT ***************** |
| |
| **PLANS NEED TO BE SUBMITTED FOR 2002 |
| NEC CODE COMPLIANCE. |
| PLEASE SEE THE FOLLOWING COMMENTS. |
| |
| 1)NOTE: PLEASE SUBMIT A COMPLETED RISER |
| DIAGRAM TO MEET CODE COMPLIANCE. |
| 215.5, 240.4,310.15B6/310.16, 240.4, |
| 250.24, 250.122 ETC |
| PLEASE SHOW A ON-LINE DIAGRAM FOR |
| SERVICE AS IF LOOKING AT FRONT ELEVATION |
| OF RISER. |
| |
| 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| RATED FOR THE AVAILABLE FAULT CURRENT. |
| PER 110.9/215.5 |
| |
| |
| 3) NOTE: PLEASE SHOW ALL RECEPTS SERVING |
| KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| -ED PER 210.8A-6 |
| |
| |
| 4)NOTE: PLEASE LIST ALL THE REQ'D |
| DEDICATED BATH(S) CIRCUIT(S) ON PANEL |
| SCHEDULE. PER 210.52D, 210.11C3 |
| |
| 5)NOTE: SMOKE DETECTORS ARE REQUIRED |
| INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| UNIT. |
| IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| TO FLOORS ABOVE AND IN THE VICINITY OF |
| BEDROOMS. |
| PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| A MIN OF 3' FROM BATHROOM DOORS AND |
| KITCHENS. |
| ABOVE PER:FBC 905.2, NFPA-72 8-1.4 |
| |
| 6)NOTE: PLEASE SUBMIT LOAD CALCULATIONS |
| TO MEET 220.31. |
| PLEASE SEE LIGHTING LOAD FOR HOUSE, THIS |
| DOES NOT CORRELATE WITH PLANS FOR SQ FT |
| AND ALSO THE AMOUNT OF CIRCUITS NEEDED. |
| SHOWS ALL 15A, #14. |
| PLEASE SEE ALL CONTINUOUS LOADS (POOL |
| PUMP, HEAT PUMP ARE TO BE SHOWN AT |
| 125%. |
| 230.42,215.3 ETC. |
| |
| 7)NOTE: PLEASE SEE MISSING RECEPTS PER |
| 210.52D IN MASTER BATH, YET AREA FOR |
| ROMAN TUB SHOWS 7-GFI RECEPTS?? |
| |
| 8)NOTE: PLEASE SEE 220.3B4. |
| PLEASE SHOW ALL RECESSED LTS BASED ON |
| MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT |
| BE FIGURED IN W/ 3W/PER SQ FT. |
| PLEASE PROVIDE FIXTURE INFORMATION ON |
| LEGEND. |
| |
| 9)NOTE: PLEAS LIST ARC FAULT PROTECTED |
| CIRCUITS ON PANEL SCHEDULE. 210.12 2002 |
| NEC. |
| |
| 10)NOTE: PLEASE SHOW LOCATION OF ALL |
| SERVICE EQUIPMENT. PLANS ONLY SHOW PANEL |
| IN STORAGE RM.215.5 |
| |
| 11)NOTE: PLEASE SEE 104.2.1 OF THE FBC |
| FOR REQUIREMENTS OF PLANS. |
| |
| 12)NOTE: PLEASE SHOW ALL A/C EUIPMENT |
| AND LOCATIONS OF THAT EQUIP. PLEASE |
| INCLUDE DISCONNETS REQUIRED FOR THIS. |
| 440.11 (COND UNITS). |
| PLEASE SHOW ANNY POSSIBLE GFI'S REQUIRED |
| FOR A/C EQUIPMENT. 210.63 |
| |
| 13)NOTE: PLEASE CORRELATE ALL A/C |
| EQUIPMENT WITH MECHNICAL PLANS. |
| PLEASE CORRELATE LOAD CALCULATIONS WITH |
| MECH PLANS ALSO. 215.5 |
| |
| ** PLEASE SEE RECEPT SPACING ON PLANS, |
| MOST RECEPT SPACING IS WAY ABOVE WHAT IS |
| NEED FOR 210.52, THESE ARE PERMITTED |
| YET SEEM TO BE MORE THAN NEEDED.** |
| |
| PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| ONLY INSERT NEW REVISED SHEETS INTO |
| COMPLETE SETS FOR REVIEW AND STAMPING. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-805-6717 |
| [email protected] |
| |
| |
| |