Plan Review Notes
Plan Review Notes For Permit 04031743
Permit Number 04031743
Review Stop E
Sequence Number 2
Notes
Date Text
2004-11-17 00:00:00*********** UNSAT *****************
  
 **PLANS NEED TO BE SUBMITTED FOR 2002
 NEC CODE COMPLIANCE.
 PLEASE SEE THE FOLLOWING COMMENTS.
  
 1)NOTE: PLEASE SUBMIT A COMPLETED RISER
 DIAGRAM TO MEET CODE COMPLIANCE.
 215.5, 240.4,310.15B6/310.16, 240.4,
 250.24, 250.122 ETC
 PLEASE SHOW A ON-LINE DIAGRAM FOR
 SERVICE AS IF LOOKING AT FRONT ELEVATION
 OF RISER.
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
  
 3) NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210.8A-6
  
  
 4)NOTE: PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
  
 5)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
  
 6)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 TO MEET 220.31.
 PLEASE SEE LIGHTING LOAD FOR HOUSE, THIS
 DOES NOT CORRELATE WITH PLANS FOR SQ FT
 AND ALSO THE AMOUNT OF CIRCUITS NEEDED.
 SHOWS ALL 15A, #14.
 PLEASE SEE ALL CONTINUOUS LOADS (POOL
 PUMP, HEAT PUMP ARE TO BE SHOWN AT
 125%.
 230.42,215.3 ETC.
  
 7)NOTE: PLEASE SEE MISSING RECEPTS PER
 210.52D IN MASTER BATH, YET AREA FOR
 ROMAN TUB SHOWS 7-GFI RECEPTS??
  
 8)NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 9)NOTE: PLEAS LIST ARC FAULT PROTECTED
 CIRCUITS ON PANEL SCHEDULE. 210.12 2002
 NEC.
  
 10)NOTE: PLEASE SHOW LOCATION OF ALL
 SERVICE EQUIPMENT. PLANS ONLY SHOW PANEL
 IN STORAGE RM.215.5
  
 11)NOTE: PLEASE SEE 104.2.1 OF THE FBC
 FOR REQUIREMENTS OF PLANS.
  
 12)NOTE: PLEASE SHOW ALL A/C EUIPMENT
 AND LOCATIONS OF THAT EQUIP. PLEASE
 INCLUDE DISCONNETS REQUIRED FOR THIS.
 440.11 (COND UNITS).
 PLEASE SHOW ANNY POSSIBLE GFI'S REQUIRED
 FOR A/C EQUIPMENT. 210.63
  
 13)NOTE: PLEASE CORRELATE ALL A/C
 EQUIPMENT WITH MECHNICAL PLANS.
 PLEASE CORRELATE LOAD CALCULATIONS WITH
 MECH PLANS ALSO. 215.5
  
 ** PLEASE SEE RECEPT SPACING ON PLANS,
 MOST RECEPT SPACING IS WAY ABOVE WHAT IS
 NEED FOR 210.52, THESE ARE PERMITTED
 YET SEEM TO BE MORE THAN NEEDED.**
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW