Plan Review Notes
Plan Review Notes For Permit 04031736
Permit Number 04031736
Review Stop E
Sequence Number 1
Notes
Date Text
2004-04-17 00:00:00*********** UNSAT **************
  
 1)NOTE: PLEASE SEE FS 471.219 FOR REQ'D
 CERTIFICATE OF AUTH # REQ'D.
 PLEASE SEE FAC 61G1-16.004 FOR ABOVE
 LICENSE # TO BE INCLUDED ON TITLE BLOCK.
  
  
 2)NOTE: PLEASE SEE 104.1.1, PLEASE
 PROVIDE MORE INFORMATION IN CHANGE OF
 USE OR PORTION OF BLDG.
 PLANS APPEAR TO SHOW A NEW RESIDENCE
 BEING BUILT INTO THE SECOND FLOOR OF A
 COMMERCIAL BLDG?
  
 3)NOTE: PLEASE SEE PLANS INDICATE OFCI
 IN LOCATIONS FOR GFCI. IS THIS THE SAME?
 STAIR LOCATION SEEMS TO SHOW WHAT APPEAR
 -S TO WALL SCONES WITH OFCI??
  
 4)NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI
 PROTECTED. 210.8A6
  
 5)NOTE: PLEASE VERIFY REQ'D RECEPTS FOR
 BATHROOM(S) PER 210.52D, 210.11C3, AND
 GFCI PER 210.8
  
 6) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
  
 7 )NOTE: PLEASE SEE MISSING REQ'D EGRESS
 LIGHTING AND/OR CLARIFY EGRESS LIGHTING
 PER 210.70 AND LS-101 5-8
 HALLWAY LEADING INTO FOYER OF UNIT APPEA
 -RS TO SHOW MEANS OF EGRESS TO OUTSIDE
 AND ALSO FROM LAUNDRY ROOM. PLEASE
 CLARIFY IF THESE ARE GRADE LEVEL ACCESS?
 PLEASE ALSO CLARIFY NEW OR EXISTING
 BATHROOM LIGHTING?
  
 8) NOTE: PLEASE SHOW OUTLET SPACING PER
 210.52. 2',6`,12` RULE.
 BEDROOM, WALL ARE LIVING RM
  
 9)NOTE: PLEASE SEE 210.52H FOR MISSING
 HALLWAY RECEPT.
  
 10)NOTE: PLEASE NOTE, WE ARE UNDER THE
 2002 NEC AND ARC FAULT PROTECTION IS
 REQ'D FOR ALL BEDROOM OUTLETS. THIS IS
 INCLUDE SD'S.
  
 11)NOTE: PLEASE CLARIFY SERVICE. SHOWS
 ONE METER, MAIN AND PANEL, YET THIS
 PANEL ONLY FEEDS WHAT APPEARS TO BE
 THIS RESIDENTIAL UNIT?
 RISER HAS A DIVISION LINE FOR BLDG EXT,
 AND APPEARS TO SHOW MAIN INSIDE?
 PLEASE SHOW LOCATION OF SERVICE/RISER
 ON PLANS. PLEASE ALSO VERIFY ADDITIONAL
 ELECTRICAL SERVICE. 230.2, 230.70, 230.
 72 ETC.
  
 12)NOTE: PLEASE SHOW LOCATION OF NEW
 COND UNIT, DISC AND RECEPT PER 440.11,
 210.63.
  
 13)NOTE: PLEASE SEE 424.3B FOR OCP OF
 AHU, HEAT. SHOWS 40A OCP FOR 10KW.
  
 14)NOTE: PANEL SCHEDULE APPEARS TO SHOW
 ONLY ONE CIRCUIT FOR 3 BEDROOMS??
  
 15)NOTE: PLEASE SEE 210.52C2 FOR GFI
 RECEPT REQ'D FOR ISLAND.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]