2004-04-17 00:00:00 | *********** UNSAT ************** |
| |
| 1)NOTE: PLEASE SEE FS 471.219 FOR REQ'D |
| CERTIFICATE OF AUTH # REQ'D. |
| PLEASE SEE FAC 61G1-16.004 FOR ABOVE |
| LICENSE # TO BE INCLUDED ON TITLE BLOCK. |
| |
| |
| 2)NOTE: PLEASE SEE 104.1.1, PLEASE |
| PROVIDE MORE INFORMATION IN CHANGE OF |
| USE OR PORTION OF BLDG. |
| PLANS APPEAR TO SHOW A NEW RESIDENCE |
| BEING BUILT INTO THE SECOND FLOOR OF A |
| COMMERCIAL BLDG? |
| |
| 3)NOTE: PLEASE SEE PLANS INDICATE OFCI |
| IN LOCATIONS FOR GFCI. IS THIS THE SAME? |
| STAIR LOCATION SEEMS TO SHOW WHAT APPEAR |
| -S TO WALL SCONES WITH OFCI?? |
| |
| 4)NOTE: PLEASE SHOW ALL RECEPTS SERVING |
| KITCHEN COUNTERSPACE AS GFI/GFI |
| PROTECTED. 210.8A6 |
| |
| 5)NOTE: PLEASE VERIFY REQ'D RECEPTS FOR |
| BATHROOM(S) PER 210.52D, 210.11C3, AND |
| GFCI PER 210.8 |
| |
| 6) NOTE: SMOKE DETECTORS ARE REQUIRED |
| INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| UNIT. |
| IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| TO FLOORS ABOVE AND IN THE VICINITY OF |
| BEDROOMS. |
| PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| A MIN OF 3' FROM BATHROOM DOORS AND |
| KITCHENS. |
| ABOVE PER:FBC 905.2, NFPA-72 8-1.4 |
| |
| 7 )NOTE: PLEASE SEE MISSING REQ'D EGRESS |
| LIGHTING AND/OR CLARIFY EGRESS LIGHTING |
| PER 210.70 AND LS-101 5-8 |
| HALLWAY LEADING INTO FOYER OF UNIT APPEA |
| -RS TO SHOW MEANS OF EGRESS TO OUTSIDE |
| AND ALSO FROM LAUNDRY ROOM. PLEASE |
| CLARIFY IF THESE ARE GRADE LEVEL ACCESS? |
| PLEASE ALSO CLARIFY NEW OR EXISTING |
| BATHROOM LIGHTING? |
| |
| 8) NOTE: PLEASE SHOW OUTLET SPACING PER |
| 210.52. 2',6`,12` RULE. |
| BEDROOM, WALL ARE LIVING RM |
| |
| 9)NOTE: PLEASE SEE 210.52H FOR MISSING |
| HALLWAY RECEPT. |
| |
| 10)NOTE: PLEASE NOTE, WE ARE UNDER THE |
| 2002 NEC AND ARC FAULT PROTECTION IS |
| REQ'D FOR ALL BEDROOM OUTLETS. THIS IS |
| INCLUDE SD'S. |
| |
| 11)NOTE: PLEASE CLARIFY SERVICE. SHOWS |
| ONE METER, MAIN AND PANEL, YET THIS |
| PANEL ONLY FEEDS WHAT APPEARS TO BE |
| THIS RESIDENTIAL UNIT? |
| RISER HAS A DIVISION LINE FOR BLDG EXT, |
| AND APPEARS TO SHOW MAIN INSIDE? |
| PLEASE SHOW LOCATION OF SERVICE/RISER |
| ON PLANS. PLEASE ALSO VERIFY ADDITIONAL |
| ELECTRICAL SERVICE. 230.2, 230.70, 230. |
| 72 ETC. |
| |
| 12)NOTE: PLEASE SHOW LOCATION OF NEW |
| COND UNIT, DISC AND RECEPT PER 440.11, |
| 210.63. |
| |
| 13)NOTE: PLEASE SEE 424.3B FOR OCP OF |
| AHU, HEAT. SHOWS 40A OCP FOR 10KW. |
| |
| 14)NOTE: PANEL SCHEDULE APPEARS TO SHOW |
| ONLY ONE CIRCUIT FOR 3 BEDROOMS?? |
| |
| 15)NOTE: PLEASE SEE 210.52C2 FOR GFI |
| RECEPT REQ'D FOR ISLAND. |
| |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |