Plan Review Notes
Plan Review Notes For Permit 04031736
Permit Number 04031736
Review Stop B
Sequence Number 1
Notes
Date Text
2004-04-28 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04031736
 ADD: 2805 N AUSTRALIAN AVE
 CONT: ROBERT A TURSO
 TEL: (561)358-4246
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 PLANS ARE IMCOMPLETE:
 A) PLANS DO NOT INDICATE WHAT TYPE OF
 OCCUPANCY ON THE 1ST FLOOR?
 B) FIRST FLOOR PLANS DO NOT INDICATE
 IF THIS IS A SINGLE TENANT USE? OR
 C) IF A TENANT SEPERATION WALL IS
 REQUIRED?
 D) 1ST FLOOR SHOW PATH OF TRAVEL FOR
 OCCUPANCY?
 E) SURVEY INDICATES THE BUILDING .5'
 AWAY FROM PROPERTY LINE, PROVIDE MIN
 MINIMUM BUILDING TYPE, ALLOWABLE
 OPENINGS AND RATING ON THIS EXTERIOR
 WALL?TABLE 600 ISSUES
 F) PLANS INDICATE A 2ND STORY W/ A
 RESIDENTIAL USE? WHAT SUB CLASS? R-1
 R-2 OR R-3.
 G) PLANS DO NOT PROVIDE OCCUPANCY
 SEPERATION BETWEEN THE UNITS BELOW
 AND THE PROPOSED RESIDENTIAL UNIT
 ABOVE.
 H) PLANS DO NOT INDICATE IF THE 2ND
 STORY IS EXISTING OR NEW?
 I) PLANS DO NOT GIVE ANY INFORMATION ON
 THE COMPONENTS AND CLADDING,
 WINDOWS
 EXTERIOR DOOR
 SKYLIGHTS
 GLASS BLOCK
 ROOFING ASSEMBLIES
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
 FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS.
 J) PLANS INDICATE IN A SWING DOOR IN-
 STALLING A NEW WINDOW IN A EXISTING
 OPENING, THE MANUFACTURER OF THE DOOR
 WILL NEED TO APPROVE CHANGE SINCE DOOR
 WAS NOT TESTED THAT WAY.
 K) PLANS INDICATE THE USE OF A NEW
 TRAFFICABLE ROOF DECK PROVIDE PRODUCT
 APPROVAL, ALSO PROVIDE ENGINEERS REPORT
 FOR THE ADDITIONAL LIVE LOADS THAT MAY
 OCCUR.
 L) EXTERIOR HANDRAIL NEEDS TO BE 42"
 HIGH,1015.2 HEIGHT. GUARDRAILS SHALL
 FORM A VERTICAL PROTECTIVE BARRIER NOT
 LESS THAN 42" HIGH.
 1015.3 OPENINGS. OPEN GUARDRAILS
 SHALL HAVE INTERMEDIATE RAILS OR ORNA-
 MENTAL PATTERNS SUCH AS A 4" DIAMETER
 SPHERE CAN NOT PASS THROUGH. A BOTTOM
 RAIL OR CURB SHALL BE PROVIDED THAT WILL
 REJECT THE PASSAGE OF 2" DIAMETER
 SPHERE.
  
 PLANS ARE INCOMPLETE A THOROUGH REVIEW
 CAN NOT BE COMPLETED AT THIS TIME. MORE
 COMMENTS MAY ARISE FROM THE ADDITIONAL
 INFORMATION REQUESTED.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026