Date |
Text |
2004-08-05 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 CHAPTER 1 |
| FBC-2001 CHAPTER 11 |
| FBC-2001 BUILDING |
| FHA-98 DESIGN MANUAL |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| 1) IF SEPARATE BLDGS., AN RPZ BACKFLOW |
| IS REQUIRED FOR EACH BLDG. SEC 608.13.2 |
| 2) IRRIGATION PLANS & PERMIT ARE REQUIR- |
| ED. SECTION 104.3.1.1 |
| 3) SEPARATE PERMIT REQUIRED FOR FOUNTAIN |
| PLEASE INDICATE IF THERE IS A DRAIN FOR |
| THE FOUNTAIN. SECTION 104.2.1 |
| 4) SHT A-3.01 SERVICE SINK IS REQUIRED |
| FOR SOUTH BUILDING. TABLE 403.1 |
| 5) SHT A-3.05 ROOF DRAIN CALCULATIONS, |
| PROVIDE INFORMATION ON ROOF AREAS. INDI- |
| CATE LOCATIONS OF AREAS "1" THRU "8". |
| ROOF PLAN SHOWS 13 AREAS PLUS LOWER ROOF |
| PLEASE CLARIFY. - INDICATE IF ROOF AREAS |
| INCLUDE ROOF AREA THAT DRAIN ONTO ROOF |
| AREA FROM ABOVE AT STAIRS AND STAIRS/EL- |
| EVATOR ROOF AREAS. - SHOW AREAS FOR COM- |
| BINATION WORKING SCUPPER/E0S ON LOWER |
| ROOF, INCLUDE/SHOW 1/2 AREA OF VERTICAL |
| WALLS IN CALCULATIONS. |
| 6) SHT A-3.06 INDICATE SPECIFICATION "A" |
| OR "B" BATHROOMS AS REQUIRED IN FHA-98 |
| DESIGN MANUAL SHTS 7.34 & 7.35. |
| 7) SHT A-3.10 ROOM 128, A CLEAR FLOOR |
| SPACE AT LEAST 30" BY 48" SHALL BE PRO- |
| VIDED IN FRONT OF THE SINK TO ALLOW FOR- |
| WARD APPROACH. |
| 8) SHT A-3.10 TURNING AREA REQUIRED IN |
| THE TOILET ROOM. SECTION 11-4.22.3 |
| 9) SHT A-3.10 SUBMIT CALCULATIONS FOR |
| MINIMUM FIXTURE FACILITIES FOR THE COM- |
| MON AREAS. SHOW SQUARE FOOTAGE FOR THE |
| LIBRARY, EXERCISE ROOM, COMMUNITY ROOM, |
| KITCHEN, OFFICE, SECRETARY ROOM, & THE |
| LAUNDRY ROOM. |
| 10) SUBMIT A DETAIL FOR DRINKING FOUNT- |
| AIN SHOWING COMPLIANCE WITH SECTION 11- |
| 4.15 AND ALL SUBSECTIONS. |
| 11) SHT A-7.03 DETAIL 12/A-703 WATER |
| CLOSET SHALL BE 18" FROM CENTER TO WALL |
| AND LAV SHALL BE MIN. 15" FROM CENTER TO |
| WALL. SEE FIGURES 28 & 32 CHAPTER 11. |
| 12) SHT A-7.03 DETAIL 12/A-7.03 OR DET- |
| AIL 13/P-7.03 INDICATE COMPLIANCE WITH |
| 11-4.19.4 EXPOSED PIPES AND SURFACES. |
| 13) SHT A-7.03 DETAIL 16/A-7.03 SHOW |
| KNEE CLEARANCE 11-4.24.3, SINK DEPTH 11- |
| 4.24.4 & EXPOSED PIPES AND SURFACES 11- |
| 4.24.6 FOR KITCHEN SINK. |
| 13) SHT P3.03 ROOF SCUPPERS, 3 AREAS OF |
| THE ROOF HAVE NO SECONDARY DRAINS. SECT- |
| ION 1503.4.2 OVERFLOW SCUPPERS SHALL BE |
| LOCATED AS CLOSE AS PRACTICAL TO REQUIR- |
| ED VERTICAL LEADERS OR DOWNSPOUST OR |
| WALL AND PARAPET SCUPPERS. |
| 14) SHT P4.02 THE RPZ BACKFLOW REQUIRED |
| FOR THE FOUNTAIN SHALL BE INSTALLED A |
| MINIMUM OF 12" ABOVE GRADE. SECTION |
| 608.13.2 |
| 15) SHT P5.01 WATER RISERS, AIR CHAMBERS |
| ARE NOT APPROVED. REMOVE ALL AIR CHAMB- |
| ERS FROM RISERS. SECTION 604.9 |
| 16) SHT P-5.01 S/1D WASH MACHINE SHALL |
| NOT DRAIN INTO THE WET VENT FOR THE BATH |
| ROOM FIXTURES. WASH MACHINE SHALL DIS- |
| CHARGE DOWNSTREAM OF THE WET VENTED FIX- |
| TURES. SECTION 909.1 |
| 17) SHT P-5.01 VENT FOR CONDENSATE STACK |
| SHALL NOT TERMINATE IN THE A/C CLOSET IF |
| THE CLOSET IS A PLENUM. |
| 18) SHT P-6.01 PLUMBING NOTES: |
| #14 - 1/4" PER FT. REQ'D FOR 2-1/2" AND |
| SMALLER PIPE. TABLE 704.1 |
| #18 - AIR CHAMBERS ARE NOT APPROVED. |
| DELETE REFERENCE FROM NOTES. 604.9 |
| 19) SUBMIT STORM RISER DIAGRAMS, AND A |
| STORM BLDG. DRAIN ISOMETRIC SHOWING ALL |
| PIPE SIZES AND SQUARE FOOTAGE AS IT ACC- |
| UMULATES IN THE SYSTEM. SEC 1104.3.1.1 |
| 20) INFORMATIONAL: IF ANY RETAIL SPACE |
| WILL BE USED FOR A RESTURANT, A GREASE |
| SYSTEM AND INTERCEPTOR SHALL BE REQUIRED |
| 21) SHTS P3.01 & P5.02 THE SANITARY BLDG |
| DRAIN ISOMETRIC AND THE GROUND LEVEL |
| PLUMBING PLAN DO NOT REFLECT EACH OTHER. |
| SEE RED LINE MARKINGS AND MAKE CORRECT- |
| IONS. SECTION 1104.2.1 |
| 22) SHT P4.02 CONDENSATE PIPING, SECTION |
| 710.3 ANY PORTION OF THE DRAINAGE SYSTEM |
| INSTALLED UNDERGROUND SHALL NOT BE LESS |
| THAN 2". |
| 23) SHT P5.02 AT THE LAUNDRY ROOM, SECT- |
| ION 706.3 DOUBLE SANITARY TEE PATTERNS |
| SHALL NOT RECIEVE THE DISCHARGE FROM |
| APPLIANCES WITH PUMPING ACTION DISCHARGE |
| - TEES SHALL BE STACKED FOR WASH MACH- |
| INES. |
| 23) ENGINEERS SHALL LEGIBLY INDICATE |
| THEIR NAME,ADDRESS AND LICENSE # ON EACH |
| SHEET. IF PRACTICING THROUGH A DULY |
| AUTHORIZED ENGINEERING BUSINESS, ENGIN- |
| EERS, ENGINEERS SHALL LEGIBLY INDICATE |
| THEIR NAME AND LICENSE NUMBER, AS WELL |
| AS, THE NAME, ADDRESS AND CERTIFICATE OF |
| AUTHORIZATION NUMBER OF THE ENGINEERING |
| BUSINESS ON EACH SHEET. A TITLE BLOCK |
| WILL SATISFY THIS REQUIREMENT. FAC |
| 61G15-23.002(2) - FS 471.025 |
| 25) LOOK FOR COMMENTS BY THE OTHER PLAN |
| REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| ON THE APPLICATION, PLANS, OR ATTACHED |
| SEPARATELY. WHEN RESUBMITTING PLANS |
| PLEASE CLEARLY INDICATE THE REVISION AND |
| REMOVE AND REPLACE ANY PAGES AS NECESS- |
| ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| THE PLANS WHEN RESUBMITTING PLANS. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN |
| BE FOUND, WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |