Plan Review Notes
Plan Review Notes For Permit 04031716
Permit Number 04031716
Review Stop P
Sequence Number 1
Notes
Date Text
2004-08-05 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FBC-2001 BUILDING
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) IF SEPARATE BLDGS., AN RPZ BACKFLOW
 IS REQUIRED FOR EACH BLDG. SEC 608.13.2
 2) IRRIGATION PLANS & PERMIT ARE REQUIR-
 ED. SECTION 104.3.1.1
 3) SEPARATE PERMIT REQUIRED FOR FOUNTAIN
 PLEASE INDICATE IF THERE IS A DRAIN FOR
 THE FOUNTAIN. SECTION 104.2.1
 4) SHT A-3.01 SERVICE SINK IS REQUIRED
 FOR SOUTH BUILDING. TABLE 403.1
 5) SHT A-3.05 ROOF DRAIN CALCULATIONS,
 PROVIDE INFORMATION ON ROOF AREAS. INDI-
 CATE LOCATIONS OF AREAS "1" THRU "8".
 ROOF PLAN SHOWS 13 AREAS PLUS LOWER ROOF
 PLEASE CLARIFY. - INDICATE IF ROOF AREAS
 INCLUDE ROOF AREA THAT DRAIN ONTO ROOF
 AREA FROM ABOVE AT STAIRS AND STAIRS/EL-
 EVATOR ROOF AREAS. - SHOW AREAS FOR COM-
 BINATION WORKING SCUPPER/E0S ON LOWER
 ROOF, INCLUDE/SHOW 1/2 AREA OF VERTICAL
 WALLS IN CALCULATIONS.
 6) SHT A-3.06 INDICATE SPECIFICATION "A"
 OR "B" BATHROOMS AS REQUIRED IN FHA-98
 DESIGN MANUAL SHTS 7.34 & 7.35.
 7) SHT A-3.10 ROOM 128, A CLEAR FLOOR
 SPACE AT LEAST 30" BY 48" SHALL BE PRO-
 VIDED IN FRONT OF THE SINK TO ALLOW FOR-
 WARD APPROACH.
 8) SHT A-3.10 TURNING AREA REQUIRED IN
 THE TOILET ROOM. SECTION 11-4.22.3
 9) SHT A-3.10 SUBMIT CALCULATIONS FOR
 MINIMUM FIXTURE FACILITIES FOR THE COM-
 MON AREAS. SHOW SQUARE FOOTAGE FOR THE
 LIBRARY, EXERCISE ROOM, COMMUNITY ROOM,
 KITCHEN, OFFICE, SECRETARY ROOM, & THE
 LAUNDRY ROOM.
 10) SUBMIT A DETAIL FOR DRINKING FOUNT-
 AIN SHOWING COMPLIANCE WITH SECTION 11-
 4.15 AND ALL SUBSECTIONS.
 11) SHT A-7.03 DETAIL 12/A-703 WATER
 CLOSET SHALL BE 18" FROM CENTER TO WALL
 AND LAV SHALL BE MIN. 15" FROM CENTER TO
 WALL. SEE FIGURES 28 & 32 CHAPTER 11.
 12) SHT A-7.03 DETAIL 12/A-7.03 OR DET-
 AIL 13/P-7.03 INDICATE COMPLIANCE WITH
 11-4.19.4 EXPOSED PIPES AND SURFACES.
 13) SHT A-7.03 DETAIL 16/A-7.03 SHOW
 KNEE CLEARANCE 11-4.24.3, SINK DEPTH 11-
 4.24.4 & EXPOSED PIPES AND SURFACES 11-
 4.24.6 FOR KITCHEN SINK.
 13) SHT P3.03 ROOF SCUPPERS, 3 AREAS OF
 THE ROOF HAVE NO SECONDARY DRAINS. SECT-
 ION 1503.4.2 OVERFLOW SCUPPERS SHALL BE
 LOCATED AS CLOSE AS PRACTICAL TO REQUIR-
 ED VERTICAL LEADERS OR DOWNSPOUST OR
 WALL AND PARAPET SCUPPERS.
 14) SHT P4.02 THE RPZ BACKFLOW REQUIRED
 FOR THE FOUNTAIN SHALL BE INSTALLED A
 MINIMUM OF 12" ABOVE GRADE. SECTION
 608.13.2
 15) SHT P5.01 WATER RISERS, AIR CHAMBERS
 ARE NOT APPROVED. REMOVE ALL AIR CHAMB-
 ERS FROM RISERS. SECTION 604.9
 16) SHT P-5.01 S/1D WASH MACHINE SHALL
 NOT DRAIN INTO THE WET VENT FOR THE BATH
 ROOM FIXTURES. WASH MACHINE SHALL DIS-
 CHARGE DOWNSTREAM OF THE WET VENTED FIX-
 TURES. SECTION 909.1
 17) SHT P-5.01 VENT FOR CONDENSATE STACK
 SHALL NOT TERMINATE IN THE A/C CLOSET IF
 THE CLOSET IS A PLENUM.
 18) SHT P-6.01 PLUMBING NOTES:
 #14 - 1/4" PER FT. REQ'D FOR 2-1/2" AND
 SMALLER PIPE. TABLE 704.1
 #18 - AIR CHAMBERS ARE NOT APPROVED.
 DELETE REFERENCE FROM NOTES. 604.9
 19) SUBMIT STORM RISER DIAGRAMS, AND A
 STORM BLDG. DRAIN ISOMETRIC SHOWING ALL
 PIPE SIZES AND SQUARE FOOTAGE AS IT ACC-
 UMULATES IN THE SYSTEM. SEC 1104.3.1.1
 20) INFORMATIONAL: IF ANY RETAIL SPACE
 WILL BE USED FOR A RESTURANT, A GREASE
 SYSTEM AND INTERCEPTOR SHALL BE REQUIRED
 21) SHTS P3.01 & P5.02 THE SANITARY BLDG
 DRAIN ISOMETRIC AND THE GROUND LEVEL
 PLUMBING PLAN DO NOT REFLECT EACH OTHER.
 SEE RED LINE MARKINGS AND MAKE CORRECT-
 IONS. SECTION 1104.2.1
 22) SHT P4.02 CONDENSATE PIPING, SECTION
 710.3 ANY PORTION OF THE DRAINAGE SYSTEM
 INSTALLED UNDERGROUND SHALL NOT BE LESS
 THAN 2".
 23) SHT P5.02 AT THE LAUNDRY ROOM, SECT-
 ION 706.3 DOUBLE SANITARY TEE PATTERNS
 SHALL NOT RECIEVE THE DISCHARGE FROM
 APPLIANCES WITH PUMPING ACTION DISCHARGE
 - TEES SHALL BE STACKED FOR WASH MACH-
 INES.
 23) ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME,ADDRESS AND LICENSE # ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2) - FS 471.025
 25) LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  