Plan Review Notes
Plan Review Notes For Permit 04031716
Permit Number 04031716
Review Stop M
Sequence Number 1
Notes
Date Text
2004-08-10 00:00:00DENIED:
 1.PROVIDE ENERGY AND MANUAL J
 CALCULATIONS IN ACCORCANCE WITH THE
 2001 FBC CHAPTER 13.
  
 2.PROVIDE OUTSIDE AIR CALCUALTIONS
 FOR THE APARTMENTS BY NATURAL MEANS PER
 2001 FBC(M) 402.2 & 402.2.1 OR 403.3.
  
 3.PLAN SHEET M3.04, DETAIL INDICATES
 6" DRYER EXHAUST AND 6" TOILET EXHAUST.
 DETAIL ALSO INDICATES A 6" & 4" IN
 SOFFIT AND APPEARS TO TERMINATE INTO A
 PLENUM BOX WITH A 12" X 8" WALL CAP.
  
 4.PLEASE NOTE DRYER EXHAUST SHALL BE
 NON-SCREENED WITH A BACKDRAFT DAMPER
 AND THE TOILET EXHAUST TERMINATION SHALL
 BE SCREENED. 2001 FBC(M) 504.4 & 401.6,
 RESPECTIVELY.
  
 5.PLEASE NOTE, EXHAUST DUCTS SHALL
 TERMINATE AS NOT TO CREATE A NUISANCE OR
 DIRECTED ONTO WALK-WAYS.2001 FBC(M)
 401.5.2.
  
 6.OUTSIDE AIR INTAKE AND EXHAUST SHALL
 BE LOCATED A MINIMUM OF 10 FT FROM LOT
 LINES OR BUILDINGS ON THE SAME LOT.
 INTAKE OPENINGS SHALL BE LOCATED A
 MINIMUM OF 10 FT FROM ANY NOXIOUS
 FUMES OR CONTAMINANT.2001 FBC(M) 401.5
 AND 401.5.1.
  
 7.PLAN SHEET M8.01, DETAIL FOR
 MOUNTING THE CONDENSOR UNIT.HEIGHT
 FROM THE ROOF SURFACE TO THE BOTTOM OF
 THE SUPPORT RAIL SHALL COMPLY WITH 2001
 FBC 1511.7
  
 8.PLEASE PROVIDE DETAIL FOR CONDENSATE
 INDICATE TERMINATION.PROVIDE A MINIMUM
 OF 12" AWAY FROM THE BUILDING STRUCTURE
 AS PER 2001 FBC 1503.4.4.
  
 9.SPECIFIC DRYERS INDICATED ON PLAN
 SHEET M8.01 SHALL BE INSTALLED FOR
 FINAL INSPECTION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.