2004-08-03 00:00:00 | ************** UNSAT *********** |
| |
| 1)NOTE: PLEASE SEE JURISDICTION NOTED |
| ON PLANS. |
| PROJECT IS UNDER THE CITY OF WEST PALM |
| BEACH. |
| |
| 2)NOTE: PLEASE SEE CIRCUITING OF SD'S, |
| SHOWN ON PANEL SCHEDULE AS BEING ON |
| A CIRCUIT WHICH IS NOT ARC FAULT |
| PROTECTED. PLEASE SEE 2002 NEC 210.12B |
| WHICH REQUIRES ALL "OUTLETS" IN BEDRMS |
| TO HAVE PROTECTION. FANS/LTS/SD'S/RECEPT |
| |
| 3)NOTE: PLEASE SEE PLANS ARE NOTED AS |
| HAVING LV AND HV IN SAME RACEWAY TO |
| ROOF FOR A/C EQUIPMENT.PLEASE PROVIDE |
| NOTE PER 300.3C1 |
| |
| 4)NOTE: PLEASE CORRELATE RANGE LOADS, |
| PANEL SCHEDULE INDICATES 7KW (8KW MIN |
| PER NEC ) AND LOAD CALCS INDICATE 9KW? |
| PLEASE CLARIFY. ARE THE RANGE UNIS |
| PLEASE CLARIFY. ARE THE RANGE UNIS |
| |
| 5)NOTE:PLEASE SEE 210.52C1 FOR MISSING |
| RECEPT ON 12" OF KITCHEN COUNTERSPACE. |
| |
| 6)NOTE: PLEASE SHOW ALL RECEPTS SERVING |
| KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| -ED. 210.8A6 |
| |
| 7)NOTE: PLEASE SEE UNIT #2 FOR SOME |
| SPACING FOR RECEPTS PER 210.52 |
| |
| 8)NOTE: PLEASE CLARIFY:LOAD CALCS |
| INDICATE TWO DIFFERENT TWO BEDROOM UNITS |
| B&C, BUT ONLY ONE OF THE TWO BEDROOM |
| UNIT LAYOUTS ARE SHOWN?? |
| |
| 9)NOTE: PLEASE SEE ALL MAINS MUST BE |
| GROUPED PER 230.72. SHUNT TRIPS ARE NOT |
| ACCEPTABLE BY THE CITY OF WEST PALM |
| BEACH FOR GROUPING OF MAINS. |
| SHUNT TRIPS ARE NOT RATED PER 230.76, |
| 230.79. |
| PLEASE PROVIDE MEANS OF DISC FOR 600A |
| EQUIPMENT IN MAIN ELECTRICAL ROOM. |
| |
| EQUIPMENT IN MAIN ELECTRICAL ROOM. |
| CLEARENCE REQUIRED OF EQUIPMENT ABOVE |
| CLEARENCE REQUIRED OF EQUIPMENT ABOVE |
| |
| 11)NOTE: PLEASE PROVIDE NOTE ON ELEC- |
| -TRICAL PLANS WHICH REFERENCEFHAR FOR |
| DEVICES AND HEIGHTS. |
| IT IS NOTED THAT THESE REQUIREMENTS ARE |
| NOTED ON BLDG PLANS. |
| |
| 12)NOTE: |
| PLEASE ALSO SHOW ALL CONTINOUS LOADS |
| AT 125% PER 215.3,230.42 ETC. |
| |
| PLEASE SEE NOTES FROM OTHER REVIEWERS |
| WHICH MAY OR MAY NOT HAVE AN AFFECT ON |
| ELECTRICAL PLANS. |
| |
| PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| ONLY INSERT NEW SHEETS INTO COMPLETE |
| SETS FOR REVIEW AND STAMPING. |
| PLEASE SEE BLDG REVIEW COMMENTS FOR |
| POSSIBLE TWO BLDG PERMITS? ETC. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |