Plan Review Notes
Plan Review Notes For Permit 04031716
Permit Number 04031716
Review Stop E
Sequence Number 1
Notes
Date Text
2004-08-03 00:00:00************** UNSAT ***********
  
 1)NOTE: PLEASE SEE JURISDICTION NOTED
 ON PLANS.
 PROJECT IS UNDER THE CITY OF WEST PALM
 BEACH.
  
 2)NOTE: PLEASE SEE CIRCUITING OF SD'S,
 SHOWN ON PANEL SCHEDULE AS BEING ON
 A CIRCUIT WHICH IS NOT ARC FAULT
 PROTECTED. PLEASE SEE 2002 NEC 210.12B
 WHICH REQUIRES ALL "OUTLETS" IN BEDRMS
 TO HAVE PROTECTION. FANS/LTS/SD'S/RECEPT
  
 3)NOTE: PLEASE SEE PLANS ARE NOTED AS
 HAVING LV AND HV IN SAME RACEWAY TO
 ROOF FOR A/C EQUIPMENT.PLEASE PROVIDE
 NOTE PER 300.3C1
  
 4)NOTE: PLEASE CORRELATE RANGE LOADS,
 PANEL SCHEDULE INDICATES 7KW (8KW MIN
 PER NEC ) AND LOAD CALCS INDICATE 9KW?
 PLEASE CLARIFY. ARE THE RANGE UNIS
 PLEASE CLARIFY. ARE THE RANGE UNIS
  
 5)NOTE:PLEASE SEE 210.52C1 FOR MISSING
 RECEPT ON 12" OF KITCHEN COUNTERSPACE.
  
 6)NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED. 210.8A6
  
 7)NOTE: PLEASE SEE UNIT #2 FOR SOME
 SPACING FOR RECEPTS PER 210.52
  
 8)NOTE: PLEASE CLARIFY:LOAD CALCS
 INDICATE TWO DIFFERENT TWO BEDROOM UNITS
 B&C, BUT ONLY ONE OF THE TWO BEDROOM
 UNIT LAYOUTS ARE SHOWN??
  
 9)NOTE: PLEASE SEE ALL MAINS MUST BE
 GROUPED PER 230.72. SHUNT TRIPS ARE NOT
 ACCEPTABLE BY THE CITY OF WEST PALM
 BEACH FOR GROUPING OF MAINS.
 SHUNT TRIPS ARE NOT RATED PER 230.76,
 230.79.
 PLEASE PROVIDE MEANS OF DISC FOR 600A
 EQUIPMENT IN MAIN ELECTRICAL ROOM.
  
 EQUIPMENT IN MAIN ELECTRICAL ROOM.
 CLEARENCE REQUIRED OF EQUIPMENT ABOVE
 CLEARENCE REQUIRED OF EQUIPMENT ABOVE
  
 11)NOTE: PLEASE PROVIDE NOTE ON ELEC-
 -TRICAL PLANS WHICH REFERENCEFHAR FOR
 DEVICES AND HEIGHTS.
 IT IS NOTED THAT THESE REQUIREMENTS ARE
 NOTED ON BLDG PLANS.
  
 12)NOTE:
 PLEASE ALSO SHOW ALL CONTINOUS LOADS
 AT 125% PER 215.3,230.42 ETC.
  
 PLEASE SEE NOTES FROM OTHER REVIEWERS
 WHICH MAY OR MAY NOT HAVE AN AFFECT ON
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
 PLEASE SEE BLDG REVIEW COMMENTS FOR
 POSSIBLE TWO BLDG PERMITS? ETC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]