Plan Review Notes
Plan Review Notes For Permit 04031716
Permit Number 04031716
Review Stop B
Sequence Number 1
Notes
Date Text
2004-07-29 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04031716
 ADD: 507 24TH ST/ 508 25TH ST
 VILLAGE CENTER APARTMENTS
 CONT: CARLISLE CONSTRUCTION, LLC
 TEL: (305)898-2198
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIW
 ACTION: DENIED
  
 THIS PLAN CAME IN UNDER A SINGLE PERMIT,
 WITH AN ALLEYWAY BETWEEN THE (2) LOTS
 THIS PROJECT WILL BE CONSIDERED AS (2)
 LOTS, (2) BUILDINGS & (2) PERMITS.
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
 FOR EACH PERMIT.
  
 2) TABLE 600 ISSUES, 2ND THROUGH 5TH
 FLOORS EXTEND PAST OR OVER THE PROPERTY
 LINE, (OVER THE ALLEYWAY) OR PUBLIC
 WAY. PROVIDE DOCUMENTATION APPROVAL FROM
 THE CITY, PLANNING AS WELL AS LEGAL.
  
 3)) THE PROPOSED BUILDING STRUCTURE
 TRANSGRESSES LEGAL BOUNDARY LINES
 BETWEEN THE LOTS WHICH COMBINE TO FORM
 'THE SITE'.SUBMIT A COPY OF THE 'UNITY
 OF TITLE' DOCUMENT SO THAT FBC TABLE 600
 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED
 NOT APPLICABLE.
 THIS REQUIREMENT WILL BE REQUIRED
 FOR BOTH PROJECTS ON BOTH SIDES OF THE
 ALLEYWAY.
  
 4) FL S. S. 553.71(7) " THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPAN
 CY CLASSIFICATION AS DEINED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS
 5,000 SQ FT IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
 105.13.1 THE ENFORCING AGENCY SHALL
 REQUIRE A SPECIAL INSPECTOR TO PERFORM
 SRUCTURAL INSPECTIONS ON A THRESHOLD
 BUILDING PURSUANT TO A STRUCTURAL INSPEC
 TION PLAN PREPARED BY THE ENGINEER OF
 RECORD. THE STRUCTURAL INSPECTION PLAN
 MUST BE SUBMITTED TO THE ENFORCING AGEN-
 CY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESH-
 OLD BUILDING. THE PURPOSE OF THE SRUCTUR
 AL INSPECTION PLAN IS TO PROVIDE SPECIF-
 IC INSPECTION PROCEDURES AND SCHEDULES
 SO THAT THE BUILDING CAN BE ADEQUATELY
 INSPECTED FOR COMPLIANCE WITH THE
 PERMITTED DOCUMENTS.
  
 5)WPB AMENDMENT 105.13.6. W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A
 SPECIAL INSPECTOR AS REQUIRED BY S.
 553.79(5) FLORIDA STATUTES TO THE MIN-
 IMUM INSPECTIONS REQUIRED BY THIS CODE.
 CONTACT HAROLD PISKURA MANAGER OF THE
 SPECIAL INSPECTOR PROGRAM AT (561)
 805-6711 FOR FURTHER INFORMATION BEFORE
 THE PERMIT MAY BE ISSUED.
  
 6)W.P.B. AMENDMENT 105.13.4.4 ALL
 PLANS FOR THE BUILDING WHICH ARE
 REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CON-
 TAIN A STATEMENT THAT, TO THE BEST OF
 THE ARCHITECT'S PR ENGINEER'S KNOWLEDGE,
 THE PLANS AND SPECIFICATIONS COMPLY WITH
 THE APPLICABLE FIRE-SAFETY STANDARDS AS
 DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 7) PROVIDE 3 CURRENT COPIES OF SIGNED &
 SEALED SURVEYS WITH PROPOSED IMPROVEMENT
 TO BE COMPLETED.
  
 8) FL BLD CODE 1804.2.2.QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 WHERE THE BEARING CAPACITY OF THE SOIL
 IS NOT DEFINITLY KNOWN OR IS IN QUESTION
 THE BUILDING OFFICIAL MAY REQUIRE EXPLOR
 ATIONS, TEST OR OTHER ADEQUATE PROOF AS
 TO THE PERMISSIBLE SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDA-
 TIONS SUBMITTED TO VERIFY BEARING CAPA-
 CITY SHALL BE CERTIFIED BY A GEOTECH-
 NICALREPORT FROM A DESIGN PROFESSIONAL
 PROPERLY LICENSED IN THE STATE OF
 FLORIDA.
  
 9) FL BLD CODE CHAP 13 ENERGY EFFICENCY
 PROVIDE ENERGY CALS/ W MANUAL "J"
  
 10) WRONG JURISDICTION, SEE LS3.00
  
 11) SEE PD 1 OF 2, PLANS INDICATE A 6%
 GRADE AT THE ACCESSIBLE PARKING SPACE &
 ACCESS ISLE. 11-4.6.3 SLOPES NOT TO
 EXCEED 1:50 OR 2%.
  
 12)SHEET A3.01 INDICATES A COLUMN DETAIL
 AT THE ENTRY TO THE ALLEY FROM DIXIE,
 NO SECTION OR PAGE? ADD INFO REQUIRED!
  
 13) SHEET LS 3.01 INDICATES THE WEST END
 OF THE PROJECT IS WITHIN 3 FT OF THE
 PROPERTY LINE, REQUIRING A 3 HR WALL.
 PROVIDE EQUIVLANT THICKNESS OF BLOCK,
 SEE TABLE 709.3.1.
  
 14) SHEET A9.01 DOOR SCHEDULE MISSING
 45 MIN RATING ON THE TRASH CHUTE TERMIN-
 ATION ROOM. TABLE705.1.2.
  
 15) A3.09 TRASH CHUTE ENCLOSURE (SHAFT)
 REQUIRES A 2HR RATED BLOCK. SHEET A7.01
 INDICATES A UL DESIGN NUMBER, BUT WE
 WILL NEED THE EQUIVALENT THICKNESS FROM
 THE BLOCK MANUFACTURER.TABLE 709.3.1.
  
 16) SHEET A3.07 PROVIDE INFORMATION,
 REQUIRED STRETCHER REQUIREMENT FOR
 ELEVATORS 3003.4.1.
  
 17) ARCHITECTURAL SHEETS INDICATE THE
 USE OF EFIS FOAM TRIM ON THE EXTERIOR OF
 THE BUILDING. ON BUILDINGS OF TYPE III,
 V AND VI CONSTRUCTION, TRIM SHALL BE SE-
 CURED TO THE WALL WITH METAL OR OTHER
 APPROVED BRACKETS OR FASTENERS. PROVIDE
 ADDTIONAL INFORMATION?
  
 18) A8.01 GUARDRAILS ARETO COMPLY WITH:
 FBC 1608.2.2THE GUARDRAIL SHALL BE
 DESIGNED AND CONSTRUCTED FOR A
 CONCENTRATED LOAD OF 200 LB APPLIED IN
 ANY DIRECTION AT THE TOP OF THE
 GUARDRAIL, A CONCENTRATED HORIZONTAL
 LOAD OF 200 LB APPLIED ON A 1 SQ FT AREA
 AT ANY POINT, AND A LINE LOAD OF 50 PLF
 APPLIED HORIZONTALLY AT THE REQUIRED
 GUARDRAIL HEIGHT WITH A SIMULTANEOUS
 LINE LOAD OF 100 PLF APPLIED VERTICALLY
 DOWNWARD ON THE TOP OF THE GUARDRAIL.
 THESE LOADS SHALL NOT BE APPLIED
 SIMULTANEOUSLY (UNLESS NOTED ABOVE) BUT
 SHALL BE APPLIED INDIVIDUALLY TO PRODUCE
 MAXIMUM STRESS IN EACH OF THE COMPONENTS
 OR SUPPORTS.SUBMIT CALCULATIONS.
  
 19)A8.02 DETAIL# 4, THERE ARE (2) ISSUES
 A) PLYWOOD SHEATHING CAN'T BE USED ON
 EXTERIOR WALLS TYPE V CONSTRUCTION.
 B) IT APPEARS THIS SAME NOTE INDICATES
 PLYWOOD TO BE USED AS SIDING?
  
 20) THIS SAME PAGE DETAIL# 2, INDICATES
 THE USE OF PLYWOOD FOR ROOF SHEATHING,
 TABLE 600 ROOF CEILING ASSEMBLIES FOR
 (1 HR PROTECTED) REQUIRES A 1HR RATING.
  
 21) S-2.01 SEE DESIGN LIVE LOADS:
 COORIDORS (ABOVE THE FIRST FLOOR) SHOLD
 BE 80 LBS. TABLE 1604.1.
  
 22) SAME PAGE WIND ZONE FOR ENTIRE CITY
 OF W.P.B. IS 140 HPH, CORRECT.ALSO THE
 EXPOSURE IS A "B" ZONE NOT A "C".
  
 23) THE LIGHT GAGE STEEL DESIGN DATA
 ALSO DOESN'T MATCH THE BUILDING DESIGN
 CRITERIA,1606.1.7/1606.1.8.
  
 24)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS FIXED & OPERABLE
 B) MULLIONS VERTICAL & HORIZONTAL
 C) EXTERIOR DOORS SOLID & GLAZED
 D) STORM SHUTTERS
 E) LOUVERS
 F) EFIS SYSTEMS
 G) TRUSS STRAPS AND ANCHORS
 H) ROOFING ASSEMBLIES
  
 25) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LIST
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE.IF THE PRODUCT DOES NOT HAVE STATE
 WIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL PER RULE 9B-72.
 SEE ATTACHMENT.
  
 26)PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING.
 FBC 1606.1.4.
  
 27)FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
 PROVIDE INFORMATION WHERE THE STORM
 SHUTTERS ARE TO BE STORED, IF STORED
 VERTICALLY HOW THEY WILL BE SUCURED SO
 THEY WILL NOT FALL OVER.
  
 28)1707.4.3 EACH EXTERIOR DOOR
 ASSEMBLY NOT COVERED BY 1707.4.2
 (GLAZED DOORS) SHALL BE LISTED AND TEST-
 ED FOR A PERIOD EQUAL TO THE QUANITY
 3600/ V WHERE THE TIME PERIOD IS IN
 SECTIONS AND V IS IN MILES PER HR TAKEN
 FROM FIGURE 1606. THE TIME PERIOD SHALL
 ALSO INCLUDE A 10 SECOND PERIOD AT A
 LOAD EQUAL TO 1.5 TIMES THE DESIGN
 PRESSURE.
  
 29) 1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 30) 1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 31) S8.01 ROOF PRESSURES, PLANS INDICATE
 NEGATIVE PRESSURES AS HIGH AS -208.6.
 FOR THE ROOFING ASSEMBLIES REPORTS, BE
 SURE TO MEET THESE PRESSURES.
  
 32) S3.00/ S7.01 SHEAR WALLS AND FOUNDA-
 TIONS THE WIDTH AND LENGTH OF FOOTINGS
 ARE GIVEN BUT NOT THE DEPTH NOR THE
 NUMBER OF BARS OR SIZE OF BARS.
  
 33) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 STRUCTURAL SHEETS DO NOT HAVE A TRUSS
 ANCHOR SCHEDULE FOR THE STEEL TRUSSES
 NORA TRUSS LAYOUT WITH UPLFT VALUES
 AND LATERAL LOADING.
  
 34) 1503.4.4 PROTECTION AGAINST DECAY &
 TERMITES. CONDENSATE LINES & ROOF DOWN
 SPOUTS SHALL DISCHARGE AT LEAST 1 FT.
 AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EX-
 TENSIONS, OR SPLASH BLOCKS.
  
 35)1511.7 ROOF MOUNTED MECHANICAL UNIT
 S SHALL BE MOUNTED ON CURBS RAISED A
 MINIMUM OF 8 INCHES ABOVE THE ROOF SUR-
 FACE, OR WHERE ROOFING MATERIALS EXTEND
 BENEATH THE UNIT, ON RAISED EQUIPMENT
 SUPPORTS PROVIDING A MINIMUM CLEARENCE
 HEIGHT IN ACCORDANCE WITH TABLE 1511.7.
  
 36) A7.02 DOESN'T HAVE ANY INFORMATION
 FOR SHAFT ENCLOSURES. 705.2.2 ALL OPEN-
 INGS THROUGH THE FLOOR AND PENETRATIONS
 THROUGH THE FLOOR SHALL BE PROTECTED BY
 A SHAFT ENCLOSURE IN ACCORDANCE WITH
 705.2.3.
  
 37)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIP-
 TION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE MAY BE FOUND, WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 (561)805-6715
 FAX: (561)659-8026