Plan Review Notes For Permit 04031709 |
Permit Number |
04031709 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-04-06 00:00:00 | DENIED: | | 1.PLEASE PROVIDE FORM 600C OR ENERGY | | & MANUAL J CALCULATIONS REQUIRED PER | | 2001 FBC CHAPTER 13 SUB-SECTION 600.0 | | METHOD A OR C. | | | | 2.PLAN INDICATES RETURN TRANSFER | | GRILLES IN THE DOOR.PLEASE NOTE, PER | | REVISED 2001 FBC(M) 601.4 EXCEPTION #2, | | WHEN SIZING THROUGH THE WALL OR DOOR | | TRANSFER GRILLES; SHALL USE 50 SQ INCHES | | (OF GRILLE AREA) TO 100 CFM OF SUPPLY | | AIR. | | | | 3.AUXILIARY DRAIN PAN WITH OVERFLOW | | PROTECTION REQUIRED PER 2001 FBC(M) | | 307.2.3 OR 307.2.4. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|