2004-04-27 00:00:00BUILDING PLANS REVIEW: FAILED
  
 1. A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2. SPECIFY ON PLANS THE DOOR FROM THE
 GARAGE TO THE CONDITIONED SPACE IS SOLID
 CORE OR INSULATED PER FBC 13-603.
  
 3. SPECIFY ON PLANS THE WINDOW IN BATH
 #3 WHICH IS WITHIN 3' HORIZONTALLY OF A
 SHOWER IS TEMPERED PER FBC 2405.2.
  
 4. SHOW TREAD WIDTH & RISER DETAIL ON
 PLANS.SEE FBC 1007.3.1.
  
 5. SPECIFY THE LENGTH/EMBED DEPTH OF THE
 3/16" TAPCON IN DETAIL #8 ON SHEET A.
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713