Plan Review Notes For Permit 04031546 |
Permit Number |
04031546 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-04-06 00:00:00 | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | | | PLEASE SUBMIT PLANS,ELECTRICAL CALCULAT- | | IONS FOR THE INTENDED SCOPE OF WORK PER | | 104.1.3, 104.2.1 FLORIDA BUILDING CODE, | | 2001 AND 215.5 NEC 2002. THIS WORK MUST | | BE PERMITTED TO, AND INSTALLED BY AN ELE | | CTRICAL CONTRACTOR PURSUANT TO CHAPTER | | 489 FLORIDA STATUTES. | | | | A RISER DIAGRAM IS REQUIRED FOR THE NEW | | SERVICE. | | | | NOTE: PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW SERVICE EQUIPMENT BEING INSTALL- | | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE | | RATED FOR THE AVAILABLE FAULT CURRENT. | | PER 110.9/215.5 | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 |
|