 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
  
 PLEASE SUBMIT PLANS,ELECTRICAL CALCULAT-
 IONS FOR THE INTENDED SCOPE OF WORK PER
 104.1.3, 104.2.1 FLORIDA BUILDING CODE,
 2001 AND 215.5 NEC 2002. THIS WORK MUST
 BE PERMITTED TO, AND INSTALLED BY AN ELE
 CTRICAL CONTRACTOR PURSUANT TO CHAPTER
 489 FLORIDA STATUTES.
  
 A RISER DIAGRAM IS REQUIRED FOR THE NEW
 SERVICE.
  
 NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  