Plan Review Notes For Permit 04031266 |
Permit Number |
04031266 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-04-02 00:00:00 | DENIED | | REFERENCE: FBC-2001 424.2 SWIMMING POOLS | | FBC-2001 CHAPTER 1 | | | | 1) FILTER AND PIPING ISOMETRIC ON SHEET | | 1 OF 6 DOES NOT SHOW A POOL HEATER, BUT | | THERE IS A SHEET ATTACHED SHOWING A | | RHEEM HEAT PUMP. PLEASE CLAIRFY IF THERE | | IS A POOL HEATER AND IF SO THE ISOMETRIC | | SHALL REFLECT THIS. - ALSO IF THERE IS A | | HEAT PUMP SEE THE FOLLOWING COMMENTS. | | 2) FBC-2001 424.2.14.1 SWIMMING POOL | | WATER HEATERS SHALL BEAR THE LABEL OF A | | RECOGNIZED TESTING AGENCY. MANUFACTURE | | SHEETS REQUIRED. (SUBMITTAL) | | 3) FBC-2001 424.2.14.2 WATER RETENTION, | | PROVIDE A POSITIVE MEANS OF RETAINING | | WATER IN THE HEATER WHEN PUMP IS SHUT | | OFF. (MANUFACTURE CUT SHEETS SUBMITTAL) | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|