Plan Review Notes
Plan Review Notes For Permit 04031266
Permit Number 04031266
Review Stop P
Sequence Number 1
Notes
Date Text
2004-04-02 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
 FBC-2001 CHAPTER 1
  
 1) FILTER AND PIPING ISOMETRIC ON SHEET
 1 OF 6 DOES NOT SHOW A POOL HEATER, BUT
 THERE IS A SHEET ATTACHED SHOWING A
 RHEEM HEAT PUMP. PLEASE CLAIRFY IF THERE
 IS A POOL HEATER AND IF SO THE ISOMETRIC
 SHALL REFLECT THIS. - ALSO IF THERE IS A
 HEAT PUMP SEE THE FOLLOWING COMMENTS.
 2) FBC-2001 424.2.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. MANUFACTURE
 SHEETS REQUIRED. (SUBMITTAL)
 3) FBC-2001 424.2.14.2 WATER RETENTION,
 PROVIDE A POSITIVE MEANS OF RETAINING
 WATER IN THE HEATER WHEN PUMP IS SHUT
 OFF. (MANUFACTURE CUT SHEETS SUBMITTAL)
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]