Plan Review Notes For Permit 04031265 |
Permit Number |
04031265 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-04-08 00:00:00 | DENIED: | | 1.PLEASE PROVIDE OUTSIDE AIR CALCS PER | | 2001 FBC(M) 403.3. | | | | 2.PLAN SHEET A-2 DOES NOT INDICATE ANY | | ANY VENTILATION FOR THE OTHER SHOW ROOM | | SPACE, IS IT EXISTING?PLEASE CLARIFY. | | | | 3.CONDENSING UNIT STAND SHALL COMPLY | | WITH 2001 FBC 1511.7 FOR THE HEIGHT | | REQUIREMENT FROM THE FINISHED ROOF TO | | THE BOTTOM OF SUPPORT RAIL, SEE | | ATTACHED. | | | | 4.A 4" MINIMUM CLEARANCE AROUND THE | | AHU IS REQUIRED FOR SEALING, INSPECTION, | | AND MAINTENANCE PER 2001 FBC(M) 603.1.3. | | | | 5.PLAN INDICATES CEILING CONSTRUCTION | | FIRE TREATED PLYWOOD & GYP BOARD. PLEASE | | INDICATE HOW THE AHU WILL BE ACCESSED. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|