2004-10-14 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 FUEL GAS |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| FBC-2001 CHAPTER 1 |
| |
| |
| FROM PREVIOUS REVIEWS NUMBERS 1 & 2 |
| 6) SHTS K1, K2, K3, & K4 - IF THE DESIGN |
| PROFESSIONAL IS AN ARCHITECT OR ENGINEER |
| LEGALLY REGISTERED UNDER THE LAWS OF THE |
| STATE REGULATING THE PRACTICE OF ARCHIT- |
| ECTURE OR ENGINEERING, THEN HE/SHE SHALL |
| AFFIX HIS/HER OFFICIAL SEAL TO SAID |
| DRAWINGS, SPECIFICATIONS AND ACCOMPANY- |
| ING DATA AS REQUIRED BY FLORIDA STATUTE. |
| SECTION 104.2.2 |
| *******NEW COMMENTS******* |
| 1D) ONLY ONE COPY OF SHTS K1, K2, K3, & |
| K4, WERE SUBMITTED WITH THE DBPR STAMP. |
| MINIMUM OF TWO SETS ARE REQUIRED AND THE |
| WORK SHEETS FROM DBPR ATTACHED TO EACH |
| SET FOR REVIEW ARE REQUIRED. SECTION |
| 104.2.1 |
| 2D) INDICATE THE TABLE USED IN THE FBC- |
| 2001 FUEL GAS CODE FOR THE SIZING OF THE |
| GAS PIPING. MOST REMOTE FIXTURE FROM THE |
| METER APPEARS TO BE THE POOL HEATER. ALL |
| PIPING SHALL BE SIZED FROM THIS DISTANCE |
| (MIN. 430' NEXT HIGHEST LENGTH IS 500') |
| 3D) SHT MP3O3-1 SHOWS 2.5 PSI METER. ALL |
| NATURAL GAS SIZING TABLES ARE 2 PSI. |
| PLEASE CLARIFY METER PRESSURE. |
| 4D) SUBMIT MANUF. SHEETS FOR GAS REGUL- |
| ATORS. |
| 5D) SEE ATTACHED SHEET CONCERNING THE |
| DESIGN PROFESSIONAL AND FS 553.80(2)(B) |
| ********WHEN RESUBMITTING PLANS********* |
| PLEASE CLEARLY INDICATE THE REVISION AND |
| REMOVE AND REPLACE ANY PAGES AS NECESS- |
| ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| THE PLANS WHEN RESUBMITTING PLANS. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN |
| BE FOUND, WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. - LOOSE SHEETS NOT ACCEPT- |
| ABLE. |
| |