Plan Review Notes For Permit 04031253 |
Permit Number |
04031253 |
|
Review Stop |
P |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2004-07-17 00:00:00 | DENIED | | REFERENCE: FBC-2001 CHAPTER 1 | | FBC-2001 FUEL GAS | | | | 1) BY REMOVING THE KITCHEN DRAWINGS, THE | | SHEETS WITH THE DBPR PLAN REVIEW STAMP, | | REQUIRED FOR PLAN REVIEW HAVE BEEN RE- | | MOVED. | | 2) FROM PREVIOUS REVIEWS: TOTAL BTU'S ON | | GAS SYSTEM AND TOTAL DEVELOPED LENGTH | | (MOST REMOTE FROM METER) SHALL BE PRO- | | VIDED TO REVIEW GAS PLANS. SUBMIT A GAS | | RISER ISOMETRIC SHOWING EXISTING PIPING | | WITH PIPE SIZE, INDICATE THE DISTANCE TO | | THE MOST REMOTE OUTLET FROM THE METER IN | | THE SYSTEM. | | 3) MANUF. SHEETS FOR THE GAS APPLIANCES | | WERE NOT SUBMITTED AND ARE REQUIRED FOR | | GAS REVIEW. THESE WHERE SUBMITTED EARL- | | IER BUT WERE NOT RESUBMITTED AT THIS | | TIME. | | 4) I WILL TRY TO CONTACT R. COMPO CON- | | CERNING THE GREASE INTERCEPTORS. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|