2004-06-03 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 FUEL GAS |
| FBC-2001 CHAPTER 1 |
| |
| 1) FROM PREVIOUS REVIEW: SHT K-2 P-14, 3 |
| SHOWN ON FLOOR PLAN, BUT PLUBMING SCHED- |
| ULE QUANTITY SHOWS 2. - PLANS SHALL BE |
| CHANGED TO CORRELATE INFORMATION ON THE |
| FLOOR PLAN AND PLUMBING SCHEDULE. - ALL |
| OTHER INFORMATION FOR BAR AREA SHALL BE |
| DELETED FROM PLAN AND SUBMITTED AS A |
| REVISION UNDER PERMIT NUMBER FOR 2B. |
| SECTION 104.2.1 |
| 3) FROM PREVIOUS REVIEW: SHT MP 303 THE |
| WATER RISER DIAGRAM DOES NOT REFLECT THE |
| FLOOR PLAN. WATER TO P-19 CONNECTS DOWN- |
| STREAM OF P-14 ON FLOOR PLAN, BUT UP- |
| STREAM ON WATER RISER DIAGRAM. PLEASE |
| CORRELATE PLANS. SECTION 104.2.1 |
| 4) FROM PREVIOUS REVIEW: GREASE INTER- |
| CEPTOR SHALL BE SIZED BY RODNEY COMPO, |
| ENVIRONMENTAL COMPLIANCE. WASTE ORD. |
| 2938-96. PHONE #(561) 837-4074. NO INDI- |
| CATION THAT MR. COMPO HAS BEEN CONTACTED |
| 5D) FROM PREVIOUS REVIEW: BTU LOAD OF |
| EACH APPLIANCE AND TOTAL BTU LOAD ON THE |
| SYSTEM. - IS THIS THE TOTAL GAS SYSTEM? |
| 5F) INDICATE THE DELIVER PRESSURE PER |
| FBC-2001 FUEL GAS CODE SEC. 402.2 RES- |
| PONSE INDICATES 2-5. PLEASE INDICATE |
| PRESSURE AS THIS WOULD INDICATE VARIBLE |
| PRESSURE IN SYSTEM. FROM PREVIOUS REVIEW |
| 5J) FROM PREVIOUS REVIEW: UNION TO BE |
| DOWNSTREAM OF MANUAL VALVE. NO UNION |
| SHOWN. - SAFETY SHUTOFF VALVE SHALL BE |
| PROVIDED WITH READY ACCESS. NOT UNDER |
| THE HOOD AND BEHIND GAS EQUIPMENT. |
| SECTION 631.13.5 |
| 6) FROM PREVIOUS REVIEW: SHTS K1, K2, K3 |
| & K4 - IF THE DESIGN PROFESSIONAL IS AN |
| ARCHITECT OR ENGINEER LEGALLY REGISTERED |
| UNDER THE LAWS OF THIS STATE REGULATING |
| THE PRACTICE OF ARCHITECTURE OR ENGIN- |
| EERING, THEN HE/SHE SHALL AFFIX HIS/HER |
| OFFICIAL SEAL TO SAID DRAWINGS, SPECIFI- |
| CATIONS AND ACCOMPANYING DATA, AS RE- |
| QUIRED BY FLORIDA STATUTE. SEC. 104.2.2. |
| |
| REVIEW BY KEN STEVENS |