Date Text
2004-03-29 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SHT K-2 P-14, 3 SHOWN ON FLOOR PLAN,
 BUT PLUMBING SCHEDULE QUANTITY SHOWS 2.
 P-46 NOT FOUND ON FLOOR PLAN.
 P-47, 2 SHOWN ON FLOOR PLAN IN THE
 LOUNGE AREA, BUT SCHEDULE QUANTITY SHOWS
 1. PLEASE CLAIRFY. SECTION 104.2.1
 2) SHT MP 303 SANT. RISER DOES NOT RE-
 FLECT THE FLOOR PLAN. P-19 FIXTURES CON-
 NECT DOWNSTREAM OF P-14 ON FLOOR PLAN,
 BUT UPSTREAM OF P-14 ON RISER DIAGRAM.
 PLEASE CLAIRFY. SECTION 104.2.1
 3) SHT MP 303 WATER RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN. SEE PREVIOUS
 COMMENT, AND P-5 WATER ON FLOOR PLAN
 SHOWS P-5 UPSTREAM OF LAST FLOOR SINK,
 BUT BETWEEN THE P-14'S ON RISER DIAGRAM.
 PLEASE CLAIRFY. SECTION 104.2.1
 4) GREASE INTECEPTOR REQUIRED SHALL BE
 SIZED BY RODNEY COMPO, ENVIRONMENTAL
 COMPLIANCE. WASTE ORD #2938-96. PHONE #
 (561) 837-4074
 5) THE FOLLOWING ARE REQUIREMENTS FOR
 THE GAS PERMIT. SEPARATE GAS PERMIT REQD
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE. MAKE SURE GAS RISER IS IN
 ISOMETRIC FORM.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF USED).
 C. TYPE OF GAS, (LP OR NATURAL)
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34). - BTU'S NOT SHOWN FOR EXHAUST
 AND MAKE UP AIR SYSTEM.
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3). - MAKE SURE
 TO GIVE THE DISTANCE TO THE MOST REMOTE
 OUTLET IN THE BUILDING, NOT IN THE KIT-
 CHEN.
 F. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 H. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 I. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 J. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE. SHOW ON ISO
 METRIC.
 6) SHEETS K1, K2, & K,3 ARE NOT SIGNED
 AND SEALED AS REQUIRED PER 61G1-16.001
 7) SHEET MP 303 CERTIFICATE OF AUTHORIZ-
 ATION REQUIRED PER 61G15-23.002(2) AND
 FS 471.025
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]